Setup Procedure For The Hardware On The 50 Hertz Unit
Determine the characteristics of the nominal voltage that is supplied for the system.
Illustration 1 g00733391
The Location of the Taps For The Configuration of Transformer "T1" and Transformer "T2"Note: Transformer "T1", transformer "T2", and transformer "T3" can be configured for 380 VAC, 400 VAC, and 415 VAC.
Configure transformer "T1" and transformer "T2" by removing the wire that is on the tap of the transformer. Place the wire on the tap that has the label for the correct voltage. See illustration 1.
Illustration 2 g00733403
(1) Color Coded Wires For The Tap Of The Transformer. (2) Fuse holder "F19"
Configure transformer "T3" by removing the color coded wire for the tap of the transformer (1). Place the color coded wires for the tap of the transformer (1) that has the label for the correct voltage on fuse holder "F19" (2). See illustration 2.
Perform the "Setup Procedure For The Software On The 50 Hertz Unit". Setup Procedure For The Software On The 50 Hertz Unit
Install the software. See Monitoring Software, "Hardware Installation" and Monitoring Software, "Software Installation".
Ensure that the system is in the Bypass Mode.
Apply power to the system.
After a connection has been established, click on the "Enter Password" menu option in order to view the "Enter User Name / Password" dialog box.
Illustration 3 g00697157
The "Enter User Name / Password" dialog box
Enter a valid "User Name" and then enter a valid "Password".After the password has been entered, the menu options will change. The menu bar will now contain a "Op. Params." option.
Illustration 4 g00733381
"Op. Params." Pull Down Menu
Click on the "Op. Params." option and select the "Op. Group 1: Nominal Voltage" menu.
Select the "Nominal Voltage" option from the list.
Illustration 5 g00733384
"Request Operating Parameter Change" dialog box
A "Request Operating Parameter Change" dialog box will open. Enter the new value for Nominal Voltage.
Click on the "SEND" button.
Illustration 6 g00733385
Display Area
After the "SEND" button has been selected, the messages in illustration 6 will be displayed.After this message has been displayed select the "Clear Password" menu option. The password will be cleared after 30 minutes if the "Clear Password" menu option is not selected.
Determine the characteristics of the nominal voltage that is supplied for the system.
Illustration 1 g00733391
The Location of the Taps For The Configuration of Transformer "T1" and Transformer "T2"Note: Transformer "T1", transformer "T2", and transformer "T3" can be configured for 380 VAC, 400 VAC, and 415 VAC.
Configure transformer "T1" and transformer "T2" by removing the wire that is on the tap of the transformer. Place the wire on the tap that has the label for the correct voltage. See illustration 1.
Illustration 2 g00733403
(1) Color Coded Wires For The Tap Of The Transformer. (2) Fuse holder "F19"
Configure transformer "T3" by removing the color coded wire for the tap of the transformer (1). Place the color coded wires for the tap of the transformer (1) that has the label for the correct voltage on fuse holder "F19" (2). See illustration 2.
Perform the "Setup Procedure For The Software On The 50 Hertz Unit". Setup Procedure For The Software On The 50 Hertz Unit
Install the software. See Monitoring Software, "Hardware Installation" and Monitoring Software, "Software Installation".
Ensure that the system is in the Bypass Mode.
Apply power to the system.
After a connection has been established, click on the "Enter Password" menu option in order to view the "Enter User Name / Password" dialog box.
Illustration 3 g00697157
The "Enter User Name / Password" dialog box
Enter a valid "User Name" and then enter a valid "Password".After the password has been entered, the menu options will change. The menu bar will now contain a "Op. Params." option.
Illustration 4 g00733381
"Op. Params." Pull Down Menu
Click on the "Op. Params." option and select the "Op. Group 1: Nominal Voltage" menu.
Select the "Nominal Voltage" option from the list.
Illustration 5 g00733384
"Request Operating Parameter Change" dialog box
A "Request Operating Parameter Change" dialog box will open. Enter the new value for Nominal Voltage.
Click on the "SEND" button.
Illustration 6 g00733385
Display Area
After the "SEND" button has been selected, the messages in illustration 6 will be displayed.After this message has been displayed select the "Clear Password" menu option. The password will be cleared after 30 minutes if the "Clear Password" menu option is not selected.
Caterpillar parts catalog:
Parts bracket Caterpillar catalog:
5327570
BRACKET AS
Caterpillar
Caterpillar
5327466
BRACKET AS
Caterpillar
Caterpillar
5327460
BRACKET AS
Caterpillar
Caterpillar
5327391
BRACKET AS
Caterpillar
Caterpillar
5327390
BRACKET AS
Caterpillar
Caterpillar
5327389
BRACKET AS
Caterpillar
Caterpillar
5329453
BRACKET AS
Caterpillar
Caterpillar
5329439
BRACKET
Caterpillar
Caterpillar
5329438
BRACKET
Caterpillar
Caterpillar
5329437
BRACKET
Caterpillar
Caterpillar
5329436
BRACKET
Caterpillar
Caterpillar
5329435
BRACKET
Caterpillar
Caterpillar