CAP AS-CONNECTOR 4747566 - Caterpillar



4747566 CAP AS-CONNECTOR Caterpillar parts
Rating:
46
Alternative (cross code) number:
CA4747566
474-7566
4747566
Caterpillar 4747566 CAP AS-CONNECTOR

Buy CAP AS-CONNECTOR 4747566 Caterpillar genuine, new aftermarket tractor parts with delivery

Number on catalog scheme:
  For full view, you need register

Cat SIS web machinery list:

Caterpillar parts catalog
SE60 V XW, SE60 VT XW Vibratory Screed JS900001-UP
AP1055 F Asphalt Paver TJ500001-UP (MACHINE) POWERED BY C7.1 Engine
AP1000 F Asphalt Paver AC400001-UP (MACHINE) POWERED BY C7.1 Engine
AP1055 F Asphalt Paver RLM00001-UP (MACHINE) POWERED BY C7.1 Engine
AP500F Asphalt Paver 44900001-UP (MACHINE) POWERED BY C4.4 Engine
AP655F & AP600F Asphalt Paver 65500001-UP (MACHINE) POWERED BY C4.4 Engine
AP600F, AP655F Asphalt Paver LR600001-UP (MACHINE) POWERED BY C7.1 Engine
SE50V, SE50VT Asphalt Screed J6K00001-UP
SE60 V Vibratory Screed JJ300001-UP
AP555F Asphalt Paver 5F500001-UP (MACHINE) POWERED BY C4.4 Engine
AP655F Asphalt Paver 45200001-UP (MACHINE) POWERED BY C4.4 Engine
AP655F Asphalt Paver 47900001-UP (MACHINE) POWERED BY C7.1 Engine
AP555F Asphalt Paver M4500001-UP (MACHINE) POWERED BY C4.4 Engine
AP655F L Asphalt Paver AC600001-UP (MACHINE) POWERED BY C7.1 Engine
SE50 VT, SE60 VT XW Asphalt Screed B8600001-UP
AP500F Asphalt Paver AF500001-UP (MACHINE) POWERED BY C4.4 Engine
AP600F Asphalt Paver JA600001-UP (MACHINE) POWERED BY C7.1 Engine
AP600F Asphalt Paver D6F00001-UP (MACHINE) POWERED BY C4.4 Engine


Information:


Personal injury or death can result from improper troubleshooting and repair procedures.The following troubleshooting and repair procedures should only be performed by qualified personnel familiar with this equipment.
Refer to this Operation and Maintenance Manual, "Generator Isolating for Maintenance" for information regarding the procedure to isolate the generator in a safe manner.Refer to Special Instruction, SEHS9124, "Cleaning and Drying of the Generator" for further necessary information.Of the following methods for drying the generator, the use of external heat is preferred.
External heat
Internal heat
Combination of external and internal heat
Circulating currentExternal heat is the most preferable method. Insulation drying time can vary from a few hours to several days. The drying time depends on the moisture content and the process for drying that is used.Note: Drying sometimes does not produce the required results. The use of a qualified rebuild shop may be necessary for dipping and drying the generator.
Illustration 1 g02175752
Typical curves of the resistance in the insulation that is drying
(1) Curve of the temperature in the windings
(2) Heat turned off.
(3) Drying time in hours
(4) Temperature in degrees celsius
(5) Curve of insulation resistance during drying process
(6) Insulation resistance in megohmsNote: When new insulation or damp insulation is being dried, the resistance will probably fall rapidly. The rapid fall in resistance is the result of the temperature being raised to a value for drying. After reaching a minimum for a given temperature, the resistance will again rise as moisture is driven out of the insulation. The actual values will vary with each situation. Refer to Illustration 2.If the windings or insulation is wet during the resistance measurement, use a 5 megohm resistor for protection in series with red positive lead. This procedure limits the voltage across the circuit under the test. Use this method until drying is well in progress and the resistance has reached an acceptable level.Check the windings after every 4 hours when either external or internal heat is used to dry the generator. Check the windings every hour when circulating current is used to dry the generator. Refer to Special Instruction, SEHS9124, "Cleaning and Drying of the Generator" for more information.Drying is complete when the tests show no increase in resistance and the resistance is above the minimum. Record these readings and compare these readings. Keep these records for future reference.
Illustration 2 g01696934
Curve of insulation resistance for windings in good condition
(1) Resistance after 30 seconds
(2) Resistance after 60 secondsIllustration 2 indicates the curve of the resistance of a normal high resistance in the windings over a period of 60 seconds. The resistance after 60 seconds will be greater than the resistance or equal to the resistance after 30 seconds .Note: If the insulation resistance after