4W5501 ENGINE AR Caterpillar parts
G399
Rating:
Alternative (cross code) number:
CA4W5501
4W-5501
4W5501
CA4W5501
4W-5501
4W5501
GAS ENGINE,
Compatible equipment models: 4W5501:
Information:
Droop Adjustment
This adjustment is only necessary for droop operation. The DROOP control sets the amount of speed regulation for the engine. The droop adjustment is only required when paralleling with utility bus or other units which are using hydromechanical governors. Since speed regulation is a function of load or power delivered, the DROOP function makes a reduction to the engine speed setting with an increase in load. The percent of speed droop is the difference between engine speed at "No Load" and engine speed at "Full Load". The percent of speed droop is expressed as a percentage of full load speed. It is calculated as follows.(No Load Speed - Full Load Speed) ? 100 / Full Load Speed = Percent of Flow LossExample
(61.8 Hz - 60 Hz) ? 100 / 60 Hz = 3 Percent DroopNormally, the percent of droop is known. The correction that is needed is the amount to increase the "No Load" setting. In this case, the "No Load" setting is calculated as follows. (100 percent + Percent of Droop) ? Full Loading Setting = No Loading SettingNote: If only 50 percent loading is possible, a "No Load" setting of 60.9 Hz would be an indication of three percent droop as shown in the Illustration 1.
Illustration 1 g00617347
Droop AdjustmentSetting Droop On System Operating Into A Commercial Bus
With the unit off the line, run the engine. Set the speed to 60 Hz ("No Load" setting). Mark this position.
Set RATED SPEED or external Speed Trim potentiometer setting above the 60 Hz reference by the percent droop required. For example, three percent droop would mean raising the speed to 61.8 Hz. Mark this potentiometer position. Return the potentiometer to 60 Hz.
Turn the "DROOP" potentiometer fully clockwise (maximum droop). Set the external Mode Switch to "DROOP".
Bring the unit on the line.
Return the RATED SPEED or external Speed Trim potentiometer to the point marked in 2.
Now make adjustment to "DROOP" potentiometer in counterclockwise direction (decreasing Droop) until Full Load (Rated) is reached.Setting Droop For An Isolated Load
Run the engine and set the Mode Switch to the "DROOP" position.
With the load removed from the engine, set RATED SPEED or external Speed Trim potentiometer to the "No Load" speed. For example, for three percent droop, speed setting would be 61.8 Hz.
Apply 100 percent of the load to the engine.
With the engine fully loaded, make an adjustment to the "DROOP" potentiometer until 60 Hz is reached.Note: For 50 Hz systems, adjust the potentiometer settings to 50 Hz. In this case, for three percent droop, speed setting would be 57.5 Hz.
This adjustment is only necessary for droop operation. The DROOP control sets the amount of speed regulation for the engine. The droop adjustment is only required when paralleling with utility bus or other units which are using hydromechanical governors. Since speed regulation is a function of load or power delivered, the DROOP function makes a reduction to the engine speed setting with an increase in load. The percent of speed droop is the difference between engine speed at "No Load" and engine speed at "Full Load". The percent of speed droop is expressed as a percentage of full load speed. It is calculated as follows.(No Load Speed - Full Load Speed) ? 100 / Full Load Speed = Percent of Flow LossExample
(61.8 Hz - 60 Hz) ? 100 / 60 Hz = 3 Percent DroopNormally, the percent of droop is known. The correction that is needed is the amount to increase the "No Load" setting. In this case, the "No Load" setting is calculated as follows. (100 percent + Percent of Droop) ? Full Loading Setting = No Loading SettingNote: If only 50 percent loading is possible, a "No Load" setting of 60.9 Hz would be an indication of three percent droop as shown in the Illustration 1.
Illustration 1 g00617347
Droop AdjustmentSetting Droop On System Operating Into A Commercial Bus
With the unit off the line, run the engine. Set the speed to 60 Hz ("No Load" setting). Mark this position.
Set RATED SPEED or external Speed Trim potentiometer setting above the 60 Hz reference by the percent droop required. For example, three percent droop would mean raising the speed to 61.8 Hz. Mark this potentiometer position. Return the potentiometer to 60 Hz.
Turn the "DROOP" potentiometer fully clockwise (maximum droop). Set the external Mode Switch to "DROOP".
Bring the unit on the line.
Return the RATED SPEED or external Speed Trim potentiometer to the point marked in 2.
Now make adjustment to "DROOP" potentiometer in counterclockwise direction (decreasing Droop) until Full Load (Rated) is reached.Setting Droop For An Isolated Load
Run the engine and set the Mode Switch to the "DROOP" position.
With the load removed from the engine, set RATED SPEED or external Speed Trim potentiometer to the "No Load" speed. For example, for three percent droop, speed setting would be 61.8 Hz.
Apply 100 percent of the load to the engine.
With the engine fully loaded, make an adjustment to the "DROOP" potentiometer until 60 Hz is reached.Note: For 50 Hz systems, adjust the potentiometer settings to 50 Hz. In this case, for three percent droop, speed setting would be 57.5 Hz.
Caterpillar SIS machinery equipment:
Parts engine Caterpillar catalog:
3N1197
ENGINE AR
G399
G399
3N3373
ENGINE AR
G399
G399
3N3340
ENGINE AR
G399
G399
3N3374
ENGINE AR
G399
G399
1013146
ENGINE AR
3116
3116
3850473
ENGINE AR-COMPLETE
906H2, 907H2, 908H2
906H2, 907H2, 908H2
3197261
ENGINE AR
D6K LGP, PL61
D6K LGP, PL61
2870105
ENGINE AR
321C
321C
1736960
ENGINE AR
3512B
3512B
1173010
ENGINE GP
AP-1000
AP-1000
1193629
ENGINE AR
3306C
3306C
3722374
ENGINE AR-PRIMARY
C4.4, C7.1
C4.4, C7.1
6C1473
ENGINE AR
G936
G936
7N3377
ENGINE AR
3306, 3512
3306, 3512