1L7425 FUEL TANK GROUP Caterpillar parts
D342
Rating:
Alternative (cross code) number:
CA1L7425
1L-7425
1L7425
CA1L7425
1L-7425
1L7425
Weight: 20 pounds 9 kg.
INDUSTRIAL ENGINE,
Compatible equipment models: 1L7425:
Information:
Problem 4
The starting motor remains engaged or the starting motor continues to run after the engine is running.
Check the components of the starting circuit.
Measure the voltages at terminal (TS-26) of the junction box and at terminal (ESS-12) of the electronic speed switch while the engine is running.Result
The voltage at both terminals is zero volts.The problem is in the starting motor (SM), the pinion solenoid (PS), or the magnetic switch (MS). Repair the faulty component. STOP.
The voltage at terminal (ESS-12) is between 15 volts and 32 volts. The voltage at terminal (TS-26) is above 15 volts or below 15 volts but not zero volts.The contacts for the crank terminate (CT) switch of the electronic speed switch (ESS) do not open. Refer to Testing and Adjusting, "Crank Terminate Speed Calibration". If the ESS is not faulty, check diode (D3). Refer to Testing and Adjusting, "Diode Test".
The voltage at both terminals is between 15 volts and 32 volts.The voltage at the terminals is greater than zero volts. During the normal operation of the start/stop switch, the start/stop switch opens across the contacts of the START position. Also, the start/stop switch closes across the contacts of the RUN position. The switch closes when the toggle or the lever of the switch moves from the START position to the RUN position. Repair the switch if the voltage is zero.
The voltage at terminal (ESS-12) is not zero.The CT contacts of the ESS are not opening. Refer to Testing and Adjusting, "Crank Terminate Speed Calibration".Problem 5
The engine shutdown occurs after the engine runs for more than 3 minutes.
Check the overspeed setting on the electronic speed switch (ESS).
Observe the indicator lamp on the ESS.
Reset the air shutoff lever, if equipped.Result
The indicator lamp on the ESS is turned on.Overspeed is indicated as the cause of the engine shutdown. Press the "RESET" button of the ESS. Find the cause of the overspeed. Refer to Testing and Adjusting, "Overspeed Verification Test" and Testing and Adjusting, "Overspeed Calibration". If the overspeed is adjusted properly and the problem persists, check the shielded cable. Only the shield should be connected to terminal 2 on the ESS. STOP.
The indicator lamp is turned off.Go to Step 2.
Check the oil pressure switches.
Connect a jumper between terminals (TS-9) and (TS-14) of the junction box.
Start the engine.Result
The engine starts and the engine runs.The problem is in the oil pressure switches. Go to Step 7 of "Problem 1".
The engine starts but engine shutdown occurs immediately.Go to Step 1 of "Problem 3".
The engine starts and the engine runs but engine shutdown occurs after the engine runs for more than 3 minutes.Go to Step 3.
The engine cranks but the engine does not start.Go to Step 1 of "Problem 1".Note: If the water temperature contactor switch causes overheating go to Step 8 of "Problem 1". If the water temperature contactor switch is not the problem, go to Step 1of "Problem 1".
Check the slave relay (SR1).
Disconnect the jumper from terminals (TS-9) and (TD-14).
Connect a jumper between terminals (TS-14) and (TD-24).
Remove the jumper
The starting motor remains engaged or the starting motor continues to run after the engine is running.
Check the components of the starting circuit.
Measure the voltages at terminal (TS-26) of the junction box and at terminal (ESS-12) of the electronic speed switch while the engine is running.Result
The voltage at both terminals is zero volts.The problem is in the starting motor (SM), the pinion solenoid (PS), or the magnetic switch (MS). Repair the faulty component. STOP.
The voltage at terminal (ESS-12) is between 15 volts and 32 volts. The voltage at terminal (TS-26) is above 15 volts or below 15 volts but not zero volts.The contacts for the crank terminate (CT) switch of the electronic speed switch (ESS) do not open. Refer to Testing and Adjusting, "Crank Terminate Speed Calibration". If the ESS is not faulty, check diode (D3). Refer to Testing and Adjusting, "Diode Test".
The voltage at both terminals is between 15 volts and 32 volts.The voltage at the terminals is greater than zero volts. During the normal operation of the start/stop switch, the start/stop switch opens across the contacts of the START position. Also, the start/stop switch closes across the contacts of the RUN position. The switch closes when the toggle or the lever of the switch moves from the START position to the RUN position. Repair the switch if the voltage is zero.
The voltage at terminal (ESS-12) is not zero.The CT contacts of the ESS are not opening. Refer to Testing and Adjusting, "Crank Terminate Speed Calibration".Problem 5
The engine shutdown occurs after the engine runs for more than 3 minutes.
Check the overspeed setting on the electronic speed switch (ESS).
Observe the indicator lamp on the ESS.
Reset the air shutoff lever, if equipped.Result
The indicator lamp on the ESS is turned on.Overspeed is indicated as the cause of the engine shutdown. Press the "RESET" button of the ESS. Find the cause of the overspeed. Refer to Testing and Adjusting, "Overspeed Verification Test" and Testing and Adjusting, "Overspeed Calibration". If the overspeed is adjusted properly and the problem persists, check the shielded cable. Only the shield should be connected to terminal 2 on the ESS. STOP.
The indicator lamp is turned off.Go to Step 2.
Check the oil pressure switches.
Connect a jumper between terminals (TS-9) and (TS-14) of the junction box.
Start the engine.Result
The engine starts and the engine runs.The problem is in the oil pressure switches. Go to Step 7 of "Problem 1".
The engine starts but engine shutdown occurs immediately.Go to Step 1 of "Problem 3".
The engine starts and the engine runs but engine shutdown occurs after the engine runs for more than 3 minutes.Go to Step 3.
The engine cranks but the engine does not start.Go to Step 1 of "Problem 1".Note: If the water temperature contactor switch causes overheating go to Step 8 of "Problem 1". If the water temperature contactor switch is not the problem, go to Step 1of "Problem 1".
Check the slave relay (SR1).
Disconnect the jumper from terminals (TS-9) and (TD-14).
Connect a jumper between terminals (TS-14) and (TD-24).
Remove the jumper
Caterpillar SIS machinery equipment:
Parts fuel Caterpillar catalog:
8H5301
FUEL FILTER GROUP
D342, D342C
D342, D342C
2S2500
FUEL PUMP HOUSING
D342, D342C, D8H
D342, D342C, D8H
1P2297
FUEL PRIMING PUMP ASSEMBLY
16, 1693, 583K, 631C, 633C, 637, 641B, 650B, 657B, 666, 666B, 768B, 769, 777, 824B, 825B, 826B, 834, 983, 988, 992, D342, D342C, D343, D346, D348, D349, D353C, D8H, D8K
16, 1693, 583K, 631C, 633C, 637, 641B, 650B, 657B, 666, 666B, 768B, 769, 777, 824B, 825B, 826B, 834, 983, 988, 992, D342, D342C, D343, D346, D348, D349, D353C, D8H, D8K
8H4716
FUEL PUMP HOUSING GROUP
583H, D342, D342C, D8H
583H, D342, D342C, D8H
3L7736
FUEL SYSTEM GROUP
D342, D342C
D342, D342C
3L8466
FUEL PRIMING PUMP GROUP
D342, D342C
D342, D342C
8D3490
FUEL TANK ADAPTER GROUP
768B, 769
768B, 769
2P1549
FUEL SYSTEM
977K
977K
2N8509
FUEL SYSTEM
3145
3145
0870490
FUEL GP-SCREED
10 FT, AP-1000, AP-800
10 FT, AP-1000, AP-800
4N3376
FUEL INJECTION LINES
980B, D6C
980B, D6C