AVSPARE.COM
parts catalog

GENERATOR AR 1440468 - Caterpillar


1440468 GENERATOR AR Caterpillar parts 3406C
Rating:
32
Alternative (cross code) number:
CA1440468
144-0468
1440468
Caterpillar 1440468 GENERATOR AR

Buy GENERATOR AR 1440468 Caterpillar genuine, new aftermarket tractor parts with delivery
GEN SET ENGINE, GENERATOR SET,

Compatible equipment models: 1440468:

GEN SET ENGINE  3406C  
GENERATOR SET  Caterpillar
  For full view, you need register

Information:


Illustration 1 g00779068
Dimensions of the VR6 Voltage Regulator (A) 212.75 mm (8.376 inch) (B) 190.50 mm (7.500 inch) (C) 161.95 mm (6.376 inch) (D) 139.70 mm (5.500 inch) (E) 87.4 mm (3.441 inch)Description of Terminals
Note: When the voltage regulator is used with a permanent magnet generator, ensure that the jumpers are removed between the following terminals: 20 - 28, 22 - 30 and 24 - 26. For regulators that were manufactured before June 2003, ensure that a jumper is installed between terminals 28 and "GND".
Table 1
Number of the Terminal    Description    
GND     Ground    
2     Auxiliary input from VAR/PF Controller    
3     Auxiliary input from VAR/PF Controller    
4     This terminal is used in conjunction with terminal 7 for selecting internal voltage adjustment. Place the jumper between terminals 4 and 7 for using internal voltage adjustment. Remote voltage adjustment requires a remote voltage adjust potentiometer between terminals 6A and 7.    
5     1 Ampere Current Transformer (CT)    
5A     5 Ampere Current Transformer (CT)    
6     Common for the Current Transformer    
6A     Common connection for selectable features    
7     This terminal is used in conjunction with terminal 4 for selecting external voltage adjustment. Place the jumper between terminals 4 and 7 for using internal voltage adjustment. Remote voltage adjustment requires a remote voltage adjust potentiometer between terminals 6A and 7.    
8     Connect terminal 8 to terminal 6A in order to select a 1 V/Hz underfrequency slope.    
9     Connect terminal 9 to terminal 6A in order to select three-phase sensing.    
20     Sensing input on phase C    
22     Sensing input on phase A    
24     Sensing input on phase B    
26     Three-phase power input    
28     Single-phase power input or three-phase power input    
30     Single-phase power input or three-phase power input    
F1     Positive field lead    
F2     Negative field lead    
Terminals 26, 28, and 30 are designed to be connected directly to a power source that is NOT switched. Either a permanent magnet or the generator's output is preferred so the voltage will gradually build. Connecting the terminals directly to a switched power source may cause damage to the regulator unless an inrush current reduction device is utilized.
Internal Adjustments
Table 2
Adjustment    Description    
"DRP"     Adjustment of the Voltage Droop    
"FAC CAL"     This is the factory calibration of the voltage adjustment range. Adjustment by the customer is not required.    
"VLT ADJ"     Voltage Adjustment    
"UF"     Underfrequency Knee Adjustment    
"STB"     Stability Adjustment    


Parts generator Caterpillar catalog:

2035755 GENERATOR GP
3512, 3512B, 3512C, 3516, SR4B
3382018 GENERATOR GP
3406C, 3456, C13, C15, C15 I6, C18, C18 I6, C9
3382009 GENERATOR AR
3406C, 3456, C13, C15, C15 I6, C18, C18 I6, C9
3247674 GENERATOR GP
3406C, 3456, C6.6, C9
3471824 GENERATOR AR
3512C, 3516, 3516B, G3520C, SR4B
2947497 GENERATOR GP
3512B, 3516, 3516B, 3516C, PM3516, PMG3516
Back to top
The names Cat, Caterpillar, John Deere, Komatsu, Volvo, Hitachi, Doosan, JCB, Hyundai or any other original equipment manufacturers are registered trademarks of the respective original equipment manufacturers. All names, descriptions, numbers and symbols are used for reference purposes only.
AVSpare.com is in no way associated with any of the manufacturers we have listed. All manufacturer's names and descriptions are for reference only. Cat® and Caterpillar® are registered trademarks of Caterpillar, Inc.