6N5474 GOVERNOR AND FUEL INJECTION PUMP GROUP Caterpillar parts
3304
Rating:
Alternative (cross code) number:
CA6N5474
6N-5474
6N5474
CA6N5474
6N-5474
6N5474
Weight: 0.30 pounds 0 kg.
MARINE ENGINE,
Compatible equipment models: 6N5474:
Information:
ALIGN="CENTER">Results    
6. Transfer Pump Inlet Regulator (TPIR) Flow Test
Refer to Illustration 1.
A. Disconnect the TPIR return line from the drain port on the TPIR. Install a suitable blanking cap on the open port in the TPIR return line.
B. Connect a temporary drain line to the drain port on the TPIR.
C. Place the end of the temporary drain line into a suitable calibrated container.
D. With the isolator switch in the ON position but the engine not running, use a suitable multimeter to measure the input voltage to the EFLP. Record the reading.
E. With the isolator switch in the ON position but the engine not running, measure the fuel flow from the temporary drain line.
F. For a 12 VDC system, refer to Illustration 2 for the minimum acceptable flow rate.
G. For a 24 VDC system, refer to Illustration 3 for the minimum acceptable flow rate.
H. Remove the temporary drain line from the drain port on the TPIR. Connect the TPIR return line to the TPIR.
   
TPIR flow rate
   
Result: The fuel flow is greater than the minimum limit.
Proceed to Test Step 9.
Result: The fuel flow is less than the minimum limit.
Proceed to Test Step 7.
   
Illustration 4 g02527498
Minimum EFLP flow rate for a 12 VDC system
Illustration 5 g02527518
Minimum EFLP flow rate for a 24 VDC system
Table 3
Troubleshooting Test Steps    Values    Results    
7. Return Pressure Relief Valve Test
A. Disconnect the return line from the secondary fuel filter base and install a blank on the line. Install a temporary line and a calibrated container to the filter base.
B. With the isolator switch in the ON position, measure fuel flow from the temporary line.
C. If the fuel flow is more than
300 mL/min (10.2 oz/min), replace the secondary fuel filter base. Refer to Disassembly and Assembly, "Fuel Filter Base - Remove and Install (Twin Secondary Fuel Filter)".
D. Remove the temporary line and reconnect the return line.
E. If the secondary fuel filter base has been replaced, attempt to start the engine. If the engine does not start, use the following procedure to check the fuel flow from the EFLP:
F. Disconnect the fuel inlet from the primary fuel filter. Place the open end of the disconnected line into a calibrated container.
G. With the isolator switch in the ON position, measure the flow from the fuel line. Refer to the Illustration 4 for the minimum acceptable fuel flow on a 12 VDC system. Refer to the Illustration 5 for the minimum acceptable fuel flow on a 24 VDC system.
   
PRV test
   
Result: The fuel flow is more than 5% below the acceptable limit.
Replace the EFLP.
Result: The fuel flow is more than 5% above the acceptable limit.
Contact the Technical Communicator at a Cat dealer.
Result: The fuel flow is within the acceptable limit.
Proceed to Test Step 8.
   
8. Check the Return Fuel Lines
A. Make sure that the TPIR return line is not blocked or kinked..
B. If the TPIR return line is clear, confirm that the Electric Fuel Lift Pump (EFLP) is operating. Make sure that fuel lines
6. Transfer Pump Inlet Regulator (TPIR) Flow Test
Refer to Illustration 1.
A. Disconnect the TPIR return line from the drain port on the TPIR. Install a suitable blanking cap on the open port in the TPIR return line.
B. Connect a temporary drain line to the drain port on the TPIR.
C. Place the end of the temporary drain line into a suitable calibrated container.
D. With the isolator switch in the ON position but the engine not running, use a suitable multimeter to measure the input voltage to the EFLP. Record the reading.
E. With the isolator switch in the ON position but the engine not running, measure the fuel flow from the temporary drain line.
F. For a 12 VDC system, refer to Illustration 2 for the minimum acceptable flow rate.
G. For a 24 VDC system, refer to Illustration 3 for the minimum acceptable flow rate.
H. Remove the temporary drain line from the drain port on the TPIR. Connect the TPIR return line to the TPIR.
   
TPIR flow rate
   
Result: The fuel flow is greater than the minimum limit.
Proceed to Test Step 9.
Result: The fuel flow is less than the minimum limit.
Proceed to Test Step 7.
   
Illustration 4 g02527498
Minimum EFLP flow rate for a 12 VDC system
Illustration 5 g02527518
Minimum EFLP flow rate for a 24 VDC system
Table 3
Troubleshooting Test Steps    Values    Results    
7. Return Pressure Relief Valve Test
A. Disconnect the return line from the secondary fuel filter base and install a blank on the line. Install a temporary line and a calibrated container to the filter base.
B. With the isolator switch in the ON position, measure fuel flow from the temporary line.
C. If the fuel flow is more than
300 mL/min (10.2 oz/min), replace the secondary fuel filter base. Refer to Disassembly and Assembly, "Fuel Filter Base - Remove and Install (Twin Secondary Fuel Filter)".
D. Remove the temporary line and reconnect the return line.
E. If the secondary fuel filter base has been replaced, attempt to start the engine. If the engine does not start, use the following procedure to check the fuel flow from the EFLP:
F. Disconnect the fuel inlet from the primary fuel filter. Place the open end of the disconnected line into a calibrated container.
G. With the isolator switch in the ON position, measure the flow from the fuel line. Refer to the Illustration 4 for the minimum acceptable fuel flow on a 12 VDC system. Refer to the Illustration 5 for the minimum acceptable fuel flow on a 24 VDC system.
   
PRV test
   
Result: The fuel flow is more than 5% below the acceptable limit.
Replace the EFLP.
Result: The fuel flow is more than 5% above the acceptable limit.
Contact the Technical Communicator at a Cat dealer.
Result: The fuel flow is within the acceptable limit.
Proceed to Test Step 8.
   
8. Check the Return Fuel Lines
A. Make sure that the TPIR return line is not blocked or kinked..
B. If the TPIR return line is clear, confirm that the Electric Fuel Lift Pump (EFLP) is operating. Make sure that fuel lines
Caterpillar SIS machinery equipment:
Caterpillar parts catalog:
Parts governor Caterpillar catalog:
6N9733
GOVERNOR GP-WOODWARD
3304, 3306
3304, 3306
4W8185
GOVERNOR GP-ELECTRONIC
3208, 3304, 3304B, 3306, 3406, 3406B, 3408, 3408C, 3412, 3412C, 3508, 3512, 3516, 3516B, C15, C18, G3306, G3406, G3408, G3408B, G3412, G3508, G3512, G3516, PM3412, SR4
3208, 3304, 3304B, 3306, 3406, 3406B, 3408, 3408C, 3412, 3412C, 3508, 3512, 3516, 3516B, C15, C18, G3306, G3406, G3408, G3408B, G3412, G3508, G3512, G3516, PM3412, SR4
4N6337
GOVERNOR GP
3304, 3306, 3406
3304, 3306, 3406
8N8597
GOVERNOR GP
3304
3304
3L4022
GOVERNOR AS
3304, 3306, D343, D353C
3304, 3306, D343, D353C
6L4349
GOVERNOR MOUNTING ASSEMBLY
3304, 3306, 3406, D330A, D330B, D333A, D333B, D334, D343
3304, 3306, 3406, D330A, D330B, D333A, D333B, D334, D343
4N4222
GOVERNOR SPRING--
14G, 1673C, 225, 235, 3304, 3306, D5, D5B, D6D
14G, 1673C, 225, 235, 3304, 3306, D5, D5B, D6D
6N7814
GOVERNOR SPRING--
3304, 3306
3304, 3306
6N7815
GOVERNOR SPRING--
3304, 3306
3304, 3306
7E7249
GOVERNOR GP
777B, 785, 789
777B, 785, 789
7N3870
GOVERNOR GP
920, 930, 941, 951B, 966C, 977L, D4D, D4E, D5, D5B, D6D
920, 930, 941, 951B, 966C, 977L, D4D, D4E, D5, D5B, D6D
1187591
GOVERNOR GP-ELECTRONIC
G3508, G3512, G3516
G3508, G3512, G3516
7N6271
GOVERNOR GP
3408, 3412, 988B
3408, 3412, 988B
7E1233
GOVERNOR AS-ELECTRONIC
3114, 3208, 3304, 3304B, 3306, 3406, 3406B, 3408, 3408C, 3412, 3412C, 3508, 3512, 3516, 3516B, C15, C18, G3306, G3408, G3408B, G3412, G3512, G3516, PM3412, SR4
3114, 3208, 3304, 3304B, 3306, 3406, 3406B, 3408, 3408C, 3412, 3412C, 3508, 3512, 3516, 3516B, C15, C18, G3306, G3408, G3408B, G3412, G3512, G3516, PM3412, SR4