Table 1
OP8 Setpoints (1) - Voltmeter Ammeter Programming    
Setpoint     Name     Description     Range Of Value     Factory Default    
AC01     Phase A (VA) Voltage Calibration     Calibration value used by the GSC+P to compensate for the characteristics of the phase A voltage transformer within the ATB+.     0 to 255 in increments of 1     0    
AC02     Phase B (VB) Voltage Calibration     Calibration value used by the GSC+P to compensate for the characteristics of the phase B voltage transformer within the ATB+.     0 to 255 in increments of 1     0    
AC03     Phase C (VC) Voltage Calibration     Calibration value used by the GSC+P to compensate for the characteristics of the phase C voltage transformer within the ATB+.     0 to 255 in increments of 1     0    
AC04     Phase A (IA) Current Calibration     Calibration value used by the GSC+P to compensate for the characteristics of the phase A current transformer within the ATB+.     0 to 255 in increments of 1     0    
AC05     Phase B (IB) Current Calibration     Calibration value used by the GSC+P to compensate for the characteristics of the phase B current transformer within the ATB+.     0 to 255 in increments of 1     0    
AC06     Phase C (IC) Current Calibration     Calibration value used by the GSC+P to compensate for the characteristics of the phase C current transformer within the ATB+.     0 to 255 in increments of 1     0    
AC07 (2)     Phase A (VA) Voltage Calibration of BTB+     Calibration value used by the GSC+P to compensate for the characteristics of the phase A voltage transformer within the BTB+.     0 to 255 in increments of one.     0    
( 1 ) The setpoints are programmed at the factory to the calibration value listed on the bar code sticker of the ATB+.
( 2 ) Setpoint is available on GSC+P only.OP8 is the option for programming the calibration value of the voltmeter and ammeter. When the GSC+P or the AC transformer box + (ATB+) has been replaced, the calibration values that are written on the ATB+ bar code sticker, must be programmed into the GSC+P in order to ensure accurate voltage values and current values.The GSC+P monitors six transformers in the ATB+ for information about the voltage and current. Each transformer has individual characteristics that affect the voltage and current measurements that are taken by the GSC+P. A calibration value is measured and the value is assigned at the factory. The calibration value is recorded on the bar code sticker that is located on the lower left hand side of the ATB+. When the generator set is assembled at the factory, the calibration values on the bar code sticker are programmed into the GSC+P. The transformers calibration value is 0 to 255. The transformers calibration value uses increments of 1.Procedure For Voltmeter/Ammeter Programming
Note: Service Mode cannot
Caterpillar parts catalog:
Parts guard Caterpillar catalog:
4465063
GUARD GP-
Caterpillar
Caterpillar
4461009
GUARD GP-
Caterpillar
Caterpillar
4454926
GUARD AS
Caterpillar
Caterpillar
4453608
GUARD AS-LH
Caterpillar
Caterpillar
4453103
GUARD AS
Caterpillar
Caterpillar
4453099
GUARD AS-
Caterpillar
Caterpillar
4485378
GUARD AS
Caterpillar
Caterpillar
4477198
GUARD GP-ALT
Caterpillar
Caterpillar
4477196
GUARD GP-ALT
Caterpillar
Caterpillar
4476833
GUARD AS-LH
Caterpillar
Caterpillar
4467871
GUARD GP-RDTR
Caterpillar
Caterpillar
4465115
GUARD AR-
Caterpillar
Caterpillar