Information:
Illustration 1 g00328626
Customer Interface Module (CIM) (1) Relay Board (2) Electronic ControlRefer to Testing And Adjusting, "Schematics And Wiring Diagrams" for more information about the Customer Interface Module (CIM).The CIM provides an interface between the GSC+P and the customer in the form of dry contacts. Separate relay contacts are the interface that is between the GSC+P and the switchgear. The two major components of CIM are the relay board (1) and the electronic control (2). The electronic control (2) and the alarm annunciator connect to the same serial data link. The operation of the CIM is similar to the operation of the alarm annunciator. The information on the data link is decoded into discrete outputs. The outputs then drive the relays that are located on the relay board (1). The relay contacts can be used to sound a horn. The relay contacts can be used to flash a lamp or the relay contacts can be used to trigger another procedure. Once an output is activated, the output remains energized until the faults that initiated the alarm are cleared. All electronic control outputs cycle at 0.5 Hz if a malfunction in the serial data link occurs. This includes the relays as well. The CIM is designed for operation when the CIM is powered by a battery system that supplies 24 DCV. The CIM is also designed for operation when the CIM is powered by a battery system that supplies 32 DCV.The available serial data link information is listed below.
High coolant temperature alarm
Low oil pressure alarm
Low coolant temperature alarm
Low oil pressure shutdown
High coolant temperature shutdown
Overcrank
Overspeed
Diagnostic fault (GSC+P)
The Engine Control Switch (ECS) is NOT in AUTO.Application Guidelines
Lamp Test
When a lamp test signal is received, the CIM activates all outputs for 10 seconds. The CIM deactivates the outputs early if the lamp test signal is deactivated. Two lamp test signals are possible. When either of the following conditions are present, the lamp test of the CIM is activated.
Terminal 5 is connected to terminal 7 of electronic control (2) .
The GSC+P lamp test signal is received over the data link.Note: When terminal 6 is connected to terminal 7 of the electronic control (2), the CIM ignores the GSC+P lamp test signal. Outputs
The relays that are on the relay board (1) are protected by fuses. The contacts are flashed with silver. The contacts are rated at 1 amp 28 DCV. The relays draw 20 mA at 24 DCV.
The outputs that are from the driver of the electronic control (2) are intended to drive the incandescent lamps or the driver outputs are intended to drive the relay loads. The driver outputs will consume a maximum of 600 mA when the voltage is 15 DCV to 45 DCV.Specifications
For installation of the CIM, the maximum distance that is between the electronic control (2) and the GSC+P is 305 m (1000 ft).
The operating voltage range is from 15 DCV to 45 DCV. 24 DCV is the nominal voltage.
The CIM is capable of operating with earth ground or operating without
Caterpillar SIS machinery equipment:
Parts guard Caterpillar catalog:
4465065
GUARD AS
Caterpillar
Caterpillar
4465063
GUARD GP-
Caterpillar
Caterpillar
4461009
GUARD GP-
Caterpillar
Caterpillar
4454926
GUARD AS
Caterpillar
Caterpillar
4453608
GUARD AS-LH
Caterpillar
Caterpillar
4453103
GUARD AS
Caterpillar
Caterpillar
4490288
GUARD
Caterpillar
Caterpillar
4485378
GUARD AS
Caterpillar
Caterpillar
4477198
GUARD GP-ALT
Caterpillar
Caterpillar
4477196
GUARD GP-ALT
Caterpillar
Caterpillar
4476833
GUARD AS-LH
Caterpillar
Caterpillar
4467871
GUARD GP-RDTR
Caterpillar
Caterpillar