Procedure A - Check Engine RPM
* If governor operation is unstable: a. Correct engine problem. Reference engine service manual.b. Go to Procedure B.Procedure B - Check for loose connections
* If connections are good: Go to Procedure C.Procedure C - Isolate Regulator
Disconnect leads F1 and F2 from their respective terminals on the regulator. Connect a 12 volt automotive type battery across exciter leads F1 and F2. Operate at half of rated speed and then slowly increase rpm.* If voltage at regulator terminals 20-22 is unstable, shutdown the generator and: a. Check connections to rotating rectifiers CR1-6 (rotating rectifier block), main field poles and other connections on the rotating (revolving) field.b. Check connections to excitor stator L1.c. Check permanent magnet (PM) exciter voltage. Disconnect wires 12 and 13 that go to the PM exciter. Check the PM exciter between wires 11-12-13 for a balanced voltage that increases with speed and is greater than 50VAC at rated speed.* If stable balanced AC voltage between regulator terminals 20-22-24 that increases with rpm: Go to Procedure D.Procedure D - Isolate Attachments
Reconnect leads to regulator terminals F1 and F2. Disconnect all attachments such as manual voltage control, remote voltage control, droop transformer, etc. If remote mounted voltage adjustment is disconnected, connect jumper across terminals 4 and 7.Check all connections to the regulator and regulator fuses.* If generator output voltage is normal: Check attachments.* If voltage at regulator terminals 20-22 is unstable at rated frequency with no load: a. Replace regulator.b. Bench test the regulator; see Bench Test.
* If governor operation is unstable: a. Correct engine problem. Reference engine service manual.b. Go to Procedure B.Procedure B - Check for loose connections
* If connections are good: Go to Procedure C.Procedure C - Isolate Regulator
Disconnect leads F1 and F2 from their respective terminals on the regulator. Connect a 12 volt automotive type battery across exciter leads F1 and F2. Operate at half of rated speed and then slowly increase rpm.* If voltage at regulator terminals 20-22 is unstable, shutdown the generator and: a. Check connections to rotating rectifiers CR1-6 (rotating rectifier block), main field poles and other connections on the rotating (revolving) field.b. Check connections to excitor stator L1.c. Check permanent magnet (PM) exciter voltage. Disconnect wires 12 and 13 that go to the PM exciter. Check the PM exciter between wires 11-12-13 for a balanced voltage that increases with speed and is greater than 50VAC at rated speed.* If stable balanced AC voltage between regulator terminals 20-22-24 that increases with rpm: Go to Procedure D.Procedure D - Isolate Attachments
Reconnect leads to regulator terminals F1 and F2. Disconnect all attachments such as manual voltage control, remote voltage control, droop transformer, etc. If remote mounted voltage adjustment is disconnected, connect jumper across terminals 4 and 7.Check all connections to the regulator and regulator fuses.* If generator output voltage is normal: Check attachments.* If voltage at regulator terminals 20-22 is unstable at rated frequency with no load: a. Replace regulator.b. Bench test the regulator; see Bench Test.
Caterpillar parts catalog:
Parts head Caterpillar catalog:
5597576
HEAD
Caterpillar
Caterpillar
5421327
HEAD AS
Caterpillar
Caterpillar
5413356
HEAD GP-PUMP
Caterpillar
Caterpillar
5331501
HEAD
Caterpillar
Caterpillar
5331500
HEAD
Caterpillar
Caterpillar
5200485
HEAD-CYLINDER
Caterpillar
Caterpillar
4382618
HEAD
Caterpillar
Caterpillar
4257736
HEAD
Caterpillar
Caterpillar
5667885
HEAD GP-MOTOR
Caterpillar
Caterpillar
5655492
HEAD
Caterpillar
Caterpillar
5599880
HEAD
Caterpillar
Caterpillar
5599872
HEAD
Caterpillar
Caterpillar