UPS/SMS with Maintenance Bypass Option
This procedure describes how to shut down the UPS/SMS when the "Maintenance Bypass Option" is present.
Transfer the UPS/SMS system to "Bypass Mode". Refer to the Testing and Adjusting, "Transfer to Bypass Mode" section of this manual for more information.
Confirm that the UPS/SMS is in "Bypass Mode" by observing the "System Mode" box on the Graphical User Interface (GUI) "One Line" page.
Open the Manintenance Bypass cabinet door. The "Transfer to Maintenance Bypass" button should illuminate with a green light.
Press and Hold the "Transfer to Maintenance Bypass" button until the green light turns off. The system transfers to "Maintenance Bypass Mode".Note: Be sure to keep the button pressed until the green light turns, indicating that transfer to Maintenance Bypass is complete.
Confirm the UPS/SMS is in Maintenance Bypass Mode by observing the Graphical User Interface (GUI) One Line diagram.The Maintenance Bypass Breaker (MBP) should be closed and the Output Isolation Switch (K5) should be open. The One Line diagram should indicate a green path or yellow path from "Maintenance Bypass Input" to "Maintenance Bypass Output".
Remove facility power from the UPS/SMS systems main input.Note: The "Maintenance Bypass Option" must have its own input from the same source.UPS/SMS without Maintenance Bypass Option
This procedure describes how to shut down the UPS/SMS when the "Mantenance Bypass Option" is not present.Note: Shut down results in a loss of load voltage unless an external wrap-around bypass is employed.
Transfer the UPS/SMS system to "Bypass Mode". Refer to the Testing and Adjusting, "Transfer to Bypass Mode" section of this manual for more information.
Confirm that the UPS/SMS is in "Bypass Mode" by observing the "System Mode" box on the Graphical User Interface (GUI) "One Line" page.Note: If an external wrap-around bypass is present, follow the applicable operating instructions to transfer to "Maintenance Bypass Mode" in order to maintain voltage to the load.Note: Ensure that the wrap-around bypass is in the correct state before continuing. Failure to do so may result in the loss of voltage to the load or a backfeed voltage on the UPS/SMS output.
Remove facility power from the UPS/SMS systems main input.
Ensure that there is no voltage present on the UPS/SMS.MMU
This procedure describes how to shut down a single MMU in a paralleled system.
Transfer the UPS/SMS system to "Offline Mode". Refer to the Testing and Adjusting, "Transfer to Bypass Mode" section of this manual for more information.
Confirm that the MMU is in "Offline Mode" by observing the "System Mode" box on the Graphical User Interface (GUI) "One Line" page.
Open the Parallel Bus Input Breaker (PIB) in the Parallel Control Cabinet (PCC), if present.
Remove facility power from the MMU systems main input.
Ensure that there is no voltage present on the MMU.Autostart to Pre-Charge
This procedure can only be done when the UPS/SMS is in "Internal Bypass Mode". Refer to the Testing and Adjusting, "Transfer to Bypass Mode" section of this manual for more information."Autostart to Pre-Charge" is done to the UPS/SMS or MMU to pre-charge the DC bus and is associated with components in the Controls,
This procedure describes how to shut down the UPS/SMS when the "Maintenance Bypass Option" is present.
Transfer the UPS/SMS system to "Bypass Mode". Refer to the Testing and Adjusting, "Transfer to Bypass Mode" section of this manual for more information.
Confirm that the UPS/SMS is in "Bypass Mode" by observing the "System Mode" box on the Graphical User Interface (GUI) "One Line" page.
Open the Manintenance Bypass cabinet door. The "Transfer to Maintenance Bypass" button should illuminate with a green light.
Press and Hold the "Transfer to Maintenance Bypass" button until the green light turns off. The system transfers to "Maintenance Bypass Mode".Note: Be sure to keep the button pressed until the green light turns, indicating that transfer to Maintenance Bypass is complete.
Confirm the UPS/SMS is in Maintenance Bypass Mode by observing the Graphical User Interface (GUI) One Line diagram.The Maintenance Bypass Breaker (MBP) should be closed and the Output Isolation Switch (K5) should be open. The One Line diagram should indicate a green path or yellow path from "Maintenance Bypass Input" to "Maintenance Bypass Output".
Remove facility power from the UPS/SMS systems main input.Note: The "Maintenance Bypass Option" must have its own input from the same source.UPS/SMS without Maintenance Bypass Option
This procedure describes how to shut down the UPS/SMS when the "Mantenance Bypass Option" is not present.Note: Shut down results in a loss of load voltage unless an external wrap-around bypass is employed.
Transfer the UPS/SMS system to "Bypass Mode". Refer to the Testing and Adjusting, "Transfer to Bypass Mode" section of this manual for more information.
Confirm that the UPS/SMS is in "Bypass Mode" by observing the "System Mode" box on the Graphical User Interface (GUI) "One Line" page.Note: If an external wrap-around bypass is present, follow the applicable operating instructions to transfer to "Maintenance Bypass Mode" in order to maintain voltage to the load.Note: Ensure that the wrap-around bypass is in the correct state before continuing. Failure to do so may result in the loss of voltage to the load or a backfeed voltage on the UPS/SMS output.
Remove facility power from the UPS/SMS systems main input.
Ensure that there is no voltage present on the UPS/SMS.MMU
This procedure describes how to shut down a single MMU in a paralleled system.
Transfer the UPS/SMS system to "Offline Mode". Refer to the Testing and Adjusting, "Transfer to Bypass Mode" section of this manual for more information.
Confirm that the MMU is in "Offline Mode" by observing the "System Mode" box on the Graphical User Interface (GUI) "One Line" page.
Open the Parallel Bus Input Breaker (PIB) in the Parallel Control Cabinet (PCC), if present.
Remove facility power from the MMU systems main input.
Ensure that there is no voltage present on the MMU.Autostart to Pre-Charge
This procedure can only be done when the UPS/SMS is in "Internal Bypass Mode". Refer to the Testing and Adjusting, "Transfer to Bypass Mode" section of this manual for more information."Autostart to Pre-Charge" is done to the UPS/SMS or MMU to pre-charge the DC bus and is associated with components in the Controls,
Caterpillar parts catalog:
Parts hose Caterpillar catalog:
6W6472
HOSE AS
235B, 235D
235B, 235D
8R5110
HOSE AS
231D, 235D
231D, 235D
9U3286
HOSE AS
235D
235D
4E8120
HOSE AS
235D
235D
6C5079
HOSE AS
231D
231D
8R8622
HOSE AS
229, 231D
229, 231D
8W7793
HOSE AS
245B, 772B, 773B, 773D, 775B, 775D
245B, 772B, 773B, 773D, 775B, 775D
8W3184
HOSE AS
245B, 789, 789B, 789C
245B, 789, 789B, 789C
6W6303
HOSE AS
225
225
6W6300
HOSE AS
225
225
6W6389
HOSE AS
235B, 235C
235B, 235C
6W6388
HOSE AS
235B, 235C
235B, 235C