9M1386 LEVER Caterpillar parts
D6C, D6D, D6E, D6G, D6G2 LGP, D6G2 XL
Rating:
Alternative (cross code) number:
CA9M1386
9M-1386
9M1386
CA9M1386
9M-1386
9M1386
Weight: 0.46 pounds 0 kg.
Information:
ARM OFFSET DIMENSION
26.6
mm
AXIS CENTERLINE TO CENTERLINE DIMENSION
31.75
mm
AXIS OFFSET DIMENSION
0
mm
FULCRUM HOLE DIAMETER
19.05
mm
LINKAGE HOLE DIAMETER
9.52
mm
TRACK-TYPE TRACTOR,
Compatible equipment models: 9M1386:
Information:
Starting Multiple Units
Multiple units are started the same as single units. Refer to Operation Section, "Single Unit Operation".Paralleling Multiple Units
Units may be paralleled at no load or paralleled with units under load. After the initial start-up conditions are satisfied, verify for the following requirements.
One of the governors can be an isochronous governor. Electronic load sharing governors are an exception.
Generators must have voltage droop compensation or cross current compensation.
Start the unit which will be paralleled.
Turn on the synchronizer lights.
After the engine has run a few minutes, bring the engine up to synchronous speed. This means that the frequency of the incoming unit will be the same as the frequency of the unit on line. The synchronizing lights will begin to blink.Note: The frequency of the incoming unit should be slightly greater than the line frequency. This condition will allow the incoming unit to assume some of the load rather than add to the system load.
Using the governor control, adjust the engine speed until the lights blink slowly.
The lights are off when the voltages of the two units are in phase. Close the breaker quickly while the lights are out.
Use governor controls in order to share kW load between engines.
Generator temperature will be stabilized in approximately 1 hour. After the generator temperature has been stabilized, adjust the voltage droop rheostat of each generator. This procedure will share the reactive load and limit the circulating currents. Less droop increases the reactive current that is carried by the generator. Adjusting the voltage droop rheostat in a counterclockwise direction (CCW) will decrease droop. Adjusting the voltage droop rheostat in a clockwise direction (CW) will increase droop. Load Division - Speed Droop (If Equipped)
Once two units have been paralleled, the units share of the kW load is determined by the governor control setting. If two units of the same capacity and the same governor characteristics have the same governor control settings, the units will share the load equally. The total load must not exceed the capacity of the one engine.In order to transfer the load from one engine to another, follow the following procedure.
Increase the governor speed control of one unit in order to increase the load.
Reduce the governor speed control of the other unit in order to decrease the load on that unit.
Raise or lower the governor speed control of both units to change system frequency.Parallel Operation Of Governors
The different governors that can be used on 3500C generator sets are shown below.
Illustration 2 g00630841
Load Sharing Module - typical exampleThe generator set load sharing module provides either droop load sharing or isochronous load sharing for paralleled generator applications. The load sharing module has a synchronizing parallel module (SPM-A) input. The module provides proportional load sharing. More information is available in the System Operation, Testing and Adjusting, SENR6565, "Generator Set Load Sensor and Generator Load Sharing Module".
Illustration 3 g00637397
(1) Droop potentiometerSpeed brick converter changes the analog signal of the speed potentiometer (SP) into a pulse width modulated (PWM) signal that the engine electronic control can recognize. The
Multiple units are started the same as single units. Refer to Operation Section, "Single Unit Operation".Paralleling Multiple Units
Units may be paralleled at no load or paralleled with units under load. After the initial start-up conditions are satisfied, verify for the following requirements.
One of the governors can be an isochronous governor. Electronic load sharing governors are an exception.
Generators must have voltage droop compensation or cross current compensation.
Start the unit which will be paralleled.
Turn on the synchronizer lights.
After the engine has run a few minutes, bring the engine up to synchronous speed. This means that the frequency of the incoming unit will be the same as the frequency of the unit on line. The synchronizing lights will begin to blink.Note: The frequency of the incoming unit should be slightly greater than the line frequency. This condition will allow the incoming unit to assume some of the load rather than add to the system load.
Using the governor control, adjust the engine speed until the lights blink slowly.
The lights are off when the voltages of the two units are in phase. Close the breaker quickly while the lights are out.
Use governor controls in order to share kW load between engines.
Generator temperature will be stabilized in approximately 1 hour. After the generator temperature has been stabilized, adjust the voltage droop rheostat of each generator. This procedure will share the reactive load and limit the circulating currents. Less droop increases the reactive current that is carried by the generator. Adjusting the voltage droop rheostat in a counterclockwise direction (CCW) will decrease droop. Adjusting the voltage droop rheostat in a clockwise direction (CW) will increase droop. Load Division - Speed Droop (If Equipped)
Once two units have been paralleled, the units share of the kW load is determined by the governor control setting. If two units of the same capacity and the same governor characteristics have the same governor control settings, the units will share the load equally. The total load must not exceed the capacity of the one engine.In order to transfer the load from one engine to another, follow the following procedure.
Increase the governor speed control of one unit in order to increase the load.
Reduce the governor speed control of the other unit in order to decrease the load on that unit.
Raise or lower the governor speed control of both units to change system frequency.Parallel Operation Of Governors
The different governors that can be used on 3500C generator sets are shown below.
Illustration 2 g00630841
Load Sharing Module - typical exampleThe generator set load sharing module provides either droop load sharing or isochronous load sharing for paralleled generator applications. The load sharing module has a synchronizing parallel module (SPM-A) input. The module provides proportional load sharing. More information is available in the System Operation, Testing and Adjusting, SENR6565, "Generator Set Load Sensor and Generator Load Sharing Module".
Illustration 3 g00637397
(1) Droop potentiometerSpeed brick converter changes the analog signal of the speed potentiometer (SP) into a pulse width modulated (PWM) signal that the engine electronic control can recognize. The
Caterpillar parts catalog:
Parts lever Caterpillar catalog:
4M1853
LEVER AS-SHIFT
1090, 1140, 1150, 1160, 1190, 1190T, 120M, 120M 2, 1290T, 12E, 12M 2, 12M 3, 12M 3 AWD, 130G, 1390, 140G, 140M, 140M 2, 140M 3, 140M 3 AWD, 14H, 14M, 16, 160M, 160M 2, 160M 3, 160M 3 AWD, 1673, 1673B,...
1090, 1140, 1150, 1160, 1190, 1190T, 120M, 120M 2, 1290T, 12E, 12M 2, 12M 3, 12M 3 AWD, 130G, 1390, 140G, 140M, 140M 2, 140M 3, 140M 3 AWD, 14H, 14M, 16, 160M, 160M 2, 160M 3, 160M 3 AWD, 1673, 1673B,...
4N0445
LEVER-LOAD STOP
120G, 12G, 130G, 140G, 1673C, 215, 225, 231D, 235, 3160, 3208, 3304, 3306, 518, 528, 613B, 613C, 627B, 637D, 639D, 920, 941, 950, 955L, 977K, 980B, CB-614, CS-551, D4D, D4E, D5, D5B, D6C, D6D, D7F, D7...
120G, 12G, 130G, 140G, 1673C, 215, 225, 231D, 235, 3160, 3208, 3304, 3306, 518, 528, 613B, 613C, 627B, 637D, 639D, 920, 941, 950, 955L, 977K, 980B, CB-614, CS-551, D4D, D4E, D5, D5B, D6C, D6D, D7F, D7...
9M7394
LEVER
120G, 120H, 120H ES, 120H NA, 120K, 120K 2, 12E, 12G, 12H, 12H ES, 12H NA, 12K, 130G, 135H, 135H NA, 140G, 140H, 140H ES, 140H NA, 140K, 140K 2, 143H, 14G, 14H, 14H NA, 16, 160G, 160H, 160H ES, 160H N...
120G, 120H, 120H ES, 120H NA, 120K, 120K 2, 12E, 12G, 12H, 12H ES, 12H NA, 12K, 130G, 135H, 135H NA, 140G, 140H, 140H ES, 140H NA, 140K, 140K 2, 143H, 14G, 14H, 14H NA, 16, 160G, 160H, 160H ES, 160H N...
8M6770
LEVER-GOVERNOR CONTROL
561C, 561D, 814B, D4E, D4E SR, D5, D5B, D5E, D6C, D6D, D6E SR
561C, 561D, 814B, D4E, D4E SR, D5, D5B, D5E, D6C, D6D, D6E SR
1V0026
LEVER
561D, 941, 955L, D4D, D4E, D4E SR, D5, D5B, D5E, D6C, D6D, D6E, D6E SR, D6F SR, D6G, D6G SR, D6G2 LGP, D6G2 XL, D7G, D7G2
561D, 941, 955L, D4D, D4E, D4E SR, D5, D5B, D5E, D6C, D6D, D6E, D6E SR, D6F SR, D6G, D6G SR, D6G2 LGP, D6G2 XL, D7G, D7G2
8J2654
LEVER ASSEM.
153, 163, D5B, D6D, D6E
153, 163, D5B, D6D, D6E
8J2653
LEVER ASSEM.
153, 163, D5B, D6D, D6E
153, 163, D5B, D6D, D6E
2319141
LEVER AS
D6G, D7G, D7G2
D6G, D7G, D7G2
2241075
LEVER AS
D6G
D6G
5A3589
LEVER ASSEM.
920, 941, 950, 953, 980C, D4E, D6C
920, 941, 950, 953, 980C, D4E, D6C
1280055
LEVER AS
D6E
D6E
8M8636
LEVER
572G, 977K, D6C, D6D, D6E, D7G
572G, 977K, D6C, D6D, D6E, D7G
9D0188
LEVER
120, 120B, 140B, 784B, 785, 785B, 789, 789B, 793, 793B, D6E, D6F SR, D6G, D6G SR, D6G2 LGP, D6G2 XL
120, 120B, 140B, 784B, 785, 785B, 789, 789B, 793, 793B, D6E, D6F SR, D6G, D6G SR, D6G2 LGP, D6G2 XL
1256114
LEVER AS
D6E, D6F SR, D6G, D6G SR
D6E, D6F SR, D6G, D6G SR
1316739
LEVER
D6E, D6F SR, D6G, D6G SR
D6E, D6F SR, D6G, D6G SR
1316742
LEVER
D6E, D6F SR, D6G, D6G SR
D6E, D6F SR, D6G, D6G SR
1363753
LEVER
904B, 904H, 910G, 914G, 933C, 939C, D3C III, D4C III, D5C III, IT14G, IT14G2, PF-290B
904B, 904H, 910G, 914G, 933C, 939C, D3C III, D4C III, D5C III, IT14G, IT14G2, PF-290B
7P7537
LEVER
933C, 939C, 943, 953, D3C III, D4C III, D5C III
933C, 939C, 943, 953, D3C III, D4C III, D5C III
1642085
LEVER AS
933C, 939C, D3C III, D4C III, D5C III
933C, 939C, D3C III, D4C III, D5C III
1171534
LEVER AS
933C, 939C, D3C III, D4C III, D5C III
933C, 939C, D3C III, D4C III, D5C III
1914794
LEVER & BUSHING AS
963C, 963D
963C, 963D
9M1385
LEVER
D6C, D6D, D6E, D6G, D6G2 LGP, D6G2 XL
D6C, D6D, D6E, D6G, D6G2 LGP, D6G2 XL