Information:
Load Connections – Generator Set Output
For units equipped with T– frame breaker: Installer shall connect conductors in accordance with separate T-frame breaker terminal instruction provided with unit. All conductors shall be sized based upon the 75° C (167° F) ampacities within Table 310-16 of the National Electrical Code, ANSI/NFPA 70, of no less than 100 percent of the maximum current that the circuit carries during rated conditions. All conductors shall be rated 90° C (194° F) or greater. For units equipped with either R-frame breaker or bus bar (terminal strip) connections: Installer shall use UL Listed terminal connectors and install in accordance with terminal connector manufacturer instructions. Terminal connectors shall be used within UL rating limit and suitable for the application. A field wiring terminal shall be sized for the connection of a conductor having an ampacity based on the 75° C (167° F) column of Table 310-16 of the National Electrical Code, ANSI/NFPA 70, of no less than 100 percent of the maximum current that the circuit carries during rated conditions. All conductors shall be rated 90° C (194° F) or greater.Equipment Ground Connection
Illustration 1 g03368914Unit ground bar shall be connected in accordance with National Electrical Code, ANSI/NFPA 70, Article 250. Installer shall use UL Listed terminal connectors and install in accordance with terminal connector manufacturer instructions. Terminal connectors shall be used within UL rating limit and suitable for the application. A field wiring ground terminal shall be sized for the connection based on the minimum ground conductor size required by UL as shown in the corresponding column of Table 1.Over-current protection devices
For units without installed circuit breaker over-current protection option, installer shall use off package mounted UL Listed circuit breaker within 7.6 m (25 feet) of generator set.
Table 1
Minimum Ground Conductor Size
AWG or kcmil (mm2)
(Amps) Copper Aluminum or copper-clad aluminum
400 1/0 (53.5) 3/0 (85.0)
500 2/0 (67.4) 4/0 (107.2)
600 2/0 (67.4) 4/0 (107.2)
800 3/0 (85.0) 250 (127)
1000 3/0 (85.0) 250 (127)
1200 3/0 (85.0) 250 (127)
1600 3/0 (85.0) 250 (127)
2000 3/0 (85.0) 250 (127)
2500 3/0 (85.0) 250 (127) Field Wiring – EMCP Controller Interface
Installer shall use Class 1 wiring methods for all controller (customer) connections with following exception. Class 2 wiring methods shall be allowed for Class 2 controller interface wiring when Class 2 conductors are shielded with UL Listed/recognized insulation sleeve or conduit rated to 600V for each individual circuit.Batteries
Servicing of batteries is to be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries.When replacing batteries, use the same number and the following type batteries:Cat Premium High Output (PHO) Batteries
Standard battery (wet) is 115-2422, BCI Group 31, Calcium Lead Alloy Grid Design, 1000 CCA,Oversize battery (wet) is 153-5710, BCI Group 4D, Calcium Lead Alloy Grid Design, 1400 CCA,Standard battery (dry) is 115-2421, BCI Group 31, Calcium Lead Alloy Grid Design, 950 CCA,Oversize battery (dry) is 9x-9730, BCI Group 4D, Low Maintenance, Hybrid Construction, 1300 CCA,
Do not dispose of battery or batteries in a fire. The battery is capable of
For units equipped with T– frame breaker: Installer shall connect conductors in accordance with separate T-frame breaker terminal instruction provided with unit. All conductors shall be sized based upon the 75° C (167° F) ampacities within Table 310-16 of the National Electrical Code, ANSI/NFPA 70, of no less than 100 percent of the maximum current that the circuit carries during rated conditions. All conductors shall be rated 90° C (194° F) or greater. For units equipped with either R-frame breaker or bus bar (terminal strip) connections: Installer shall use UL Listed terminal connectors and install in accordance with terminal connector manufacturer instructions. Terminal connectors shall be used within UL rating limit and suitable for the application. A field wiring terminal shall be sized for the connection of a conductor having an ampacity based on the 75° C (167° F) column of Table 310-16 of the National Electrical Code, ANSI/NFPA 70, of no less than 100 percent of the maximum current that the circuit carries during rated conditions. All conductors shall be rated 90° C (194° F) or greater.Equipment Ground Connection
Illustration 1 g03368914Unit ground bar shall be connected in accordance with National Electrical Code, ANSI/NFPA 70, Article 250. Installer shall use UL Listed terminal connectors and install in accordance with terminal connector manufacturer instructions. Terminal connectors shall be used within UL rating limit and suitable for the application. A field wiring ground terminal shall be sized for the connection based on the minimum ground conductor size required by UL as shown in the corresponding column of Table 1.Over-current protection devices
For units without installed circuit breaker over-current protection option, installer shall use off package mounted UL Listed circuit breaker within 7.6 m (25 feet) of generator set.
Table 1
Minimum Ground Conductor Size
AWG or kcmil (mm2)
(Amps) Copper Aluminum or copper-clad aluminum
400 1/0 (53.5) 3/0 (85.0)
500 2/0 (67.4) 4/0 (107.2)
600 2/0 (67.4) 4/0 (107.2)
800 3/0 (85.0) 250 (127)
1000 3/0 (85.0) 250 (127)
1200 3/0 (85.0) 250 (127)
1600 3/0 (85.0) 250 (127)
2000 3/0 (85.0) 250 (127)
2500 3/0 (85.0) 250 (127) Field Wiring – EMCP Controller Interface
Installer shall use Class 1 wiring methods for all controller (customer) connections with following exception. Class 2 wiring methods shall be allowed for Class 2 controller interface wiring when Class 2 conductors are shielded with UL Listed/recognized insulation sleeve or conduit rated to 600V for each individual circuit.Batteries
Servicing of batteries is to be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries.When replacing batteries, use the same number and the following type batteries:Cat Premium High Output (PHO) Batteries
Standard battery (wet) is 115-2422, BCI Group 31, Calcium Lead Alloy Grid Design, 1000 CCA,Oversize battery (wet) is 153-5710, BCI Group 4D, Calcium Lead Alloy Grid Design, 1400 CCA,Standard battery (dry) is 115-2421, BCI Group 31, Calcium Lead Alloy Grid Design, 950 CCA,Oversize battery (dry) is 9x-9730, BCI Group 4D, Low Maintenance, Hybrid Construction, 1300 CCA,
Do not dispose of battery or batteries in a fire. The battery is capable of
Caterpillar parts catalog:
Parts link Caterpillar catalog:
5042107
LINK AS
Caterpillar
Caterpillar
4887215
LINK GP-STEERING
Caterpillar
Caterpillar
4589644
LINK AS-LIFT
Caterpillar
Caterpillar
4528500
LINK GP-LIFT
Caterpillar
Caterpillar
4524030
LINK GP-LIFT
Caterpillar
Caterpillar
3903741
LINK AS
Caterpillar
Caterpillar
1758019
LINK AS.-TRACK
Caterpillar
Caterpillar
4315268
LINK AS-YM
Caterpillar
Caterpillar
5578529
LINK AS-TRACK
Caterpillar
Caterpillar
5306356
LINK
Caterpillar
Caterpillar
5243181
LINK AS-TRACK
Caterpillar
Caterpillar
5130098
LINK-TRACK
Caterpillar
Caterpillar