7E3559 MUFFLER AS Caterpillar parts
966F
Rating:
Alternative (cross code) number:
CA7E3559
7E-3559
7E3559
CA7E3559
7E-3559
7E3559
Weight: 28 pounds 12 kg.
WHEEL LOADER,
Compatible equipment models: 7E3559:
Information:
Fault Shutdown Output Driver
The fault shutdown driver is intended to provide an external signal to operate a circuit breaker shunt trip and other alarm lights and/or horns in the event of a shutdown fault. The fault shutdown driver is normally pulled low (sinking up to 100 mA). When a fault occurs the output driver will open, allowing the output to go high, to +24 VDC.Note: The output driver is "pull down" only. It will not source current when a fault occurs. Use input terminal 50 for a current source. Refer to the Customer Options illustration in Testing And Adjusting, "Wiring Diagrams".This method was chosen as a safety feature to protect against loss of battery voltage which will also cause the regulator to cease operation and, therefore, the generator voltage to collapse.Alarm Output Driver
The alarm driver is intended to provide an external signal to operate alarm lights and/or horns in the event of an alarm fault condition. The alarm driver is normally pulled low (sinking up to 100 mA). When an alarm occurs, the output driver will open, allowing the output to go high, to +24 VDC.Note: The output driver is "pull down" only. It will not source current when a fault occurs. Use input terminal 50 for a current source. Refer to the Customer Options illustration in Testing And Adjusting, "Wiring Diagrams".Note: The alarm output and fault shutdown output drivers may change state during engine cranking, indicating a false alarm or shutdown fault condition. If the "B+"/"B-" inputs to the digital voltage regulator are supplied from the engine cranking batteries, it is likely that insufficient voltage will be present during cranking. Therefore, during cranking the state of the fault shutdown output driver may change. The fault shutdown output driver should be ignored until the crank terminate speed has been reached.Excitation Disable
The excitation disable switch is intended to provide a method of disabling the regulator field output (F1 and F2) in a manner which is safe for the regulator internal components. This feature is activated by shorting terminal 42 to terminal 50. Refer to the Customer Options illustration in Testing And Adjusting, "Wiring Diagrams". Activation of the excitation disable switch will also disable the undervoltage shutdown fault.
The generator will always have residual voltage still remaining; therefore, it is important to stop the generator set if downstream maintenance is to be performed.
Fault Reset
The fault reset contact is provided as a method to reset a resettable shutdown fault through the use of an external switch. This operation is equivalent to using parameter :96 in the user interface. Operating the fault reset contact (momentarily shorting terminal 43 to terminal 50) will reset a resettable fault and allow the voltage to build again. However, on the "original" fault handling versions, the display will still show the flashing fault and the fault will remain in the active position in memory. On the "new" fault handling versions, the display will stop flashing, return to showing ":01", and the fault will remain in the active fault
The fault shutdown driver is intended to provide an external signal to operate a circuit breaker shunt trip and other alarm lights and/or horns in the event of a shutdown fault. The fault shutdown driver is normally pulled low (sinking up to 100 mA). When a fault occurs the output driver will open, allowing the output to go high, to +24 VDC.Note: The output driver is "pull down" only. It will not source current when a fault occurs. Use input terminal 50 for a current source. Refer to the Customer Options illustration in Testing And Adjusting, "Wiring Diagrams".This method was chosen as a safety feature to protect against loss of battery voltage which will also cause the regulator to cease operation and, therefore, the generator voltage to collapse.Alarm Output Driver
The alarm driver is intended to provide an external signal to operate alarm lights and/or horns in the event of an alarm fault condition. The alarm driver is normally pulled low (sinking up to 100 mA). When an alarm occurs, the output driver will open, allowing the output to go high, to +24 VDC.Note: The output driver is "pull down" only. It will not source current when a fault occurs. Use input terminal 50 for a current source. Refer to the Customer Options illustration in Testing And Adjusting, "Wiring Diagrams".Note: The alarm output and fault shutdown output drivers may change state during engine cranking, indicating a false alarm or shutdown fault condition. If the "B+"/"B-" inputs to the digital voltage regulator are supplied from the engine cranking batteries, it is likely that insufficient voltage will be present during cranking. Therefore, during cranking the state of the fault shutdown output driver may change. The fault shutdown output driver should be ignored until the crank terminate speed has been reached.Excitation Disable
The excitation disable switch is intended to provide a method of disabling the regulator field output (F1 and F2) in a manner which is safe for the regulator internal components. This feature is activated by shorting terminal 42 to terminal 50. Refer to the Customer Options illustration in Testing And Adjusting, "Wiring Diagrams". Activation of the excitation disable switch will also disable the undervoltage shutdown fault.
The generator will always have residual voltage still remaining; therefore, it is important to stop the generator set if downstream maintenance is to be performed.
Fault Reset
The fault reset contact is provided as a method to reset a resettable shutdown fault through the use of an external switch. This operation is equivalent to using parameter :96 in the user interface. Operating the fault reset contact (momentarily shorting terminal 43 to terminal 50) will reset a resettable fault and allow the voltage to build again. However, on the "original" fault handling versions, the display will still show the flashing fault and the fault will remain in the active position in memory. On the "new" fault handling versions, the display will stop flashing, return to showing ":01", and the fault will remain in the active fault
Caterpillar parts catalog:
Parts muffler Caterpillar catalog:
7E3544
MUFFLER GP
966F, 966F II
966F, 966F II
1018740
MUFFLER AS
966F, 966F II
966F, 966F II
7N9674
MUFFLER AS
826C, 980C, 980F
826C, 980C, 980F
7N1393
MUFFLER AS
824C, 826C, 980C, 980F
824C, 826C, 980C, 980F
7W8556
MUFFLER AS
834B, 988B
834B, 988B
2W9318
MUFFLER AS
834B, 988B
834B, 988B
9Y8562
MUFFLER AS
834B, 988B
834B, 988B
1529716
MUFFLER AS
966F II, 970F
966F II, 970F
1018740
MUFFLER AS
966F, 966F II
966F, 966F II
6I2408
MUFFLER AS
814F, 815F, 816F, 966F II, 970F
814F, 815F, 816F, 966F II, 970F
6I3662
MUFFLER AS
950F, 950F II, 960F
950F, 950F II, 960F
4P2496
MUFFLER AS
988F, 988F II
988F, 988F II
7E2944
MUFFLER AS
950F, 950F II
950F, 950F II