Condition: The circuit breakers immediately trip after starting the screed heating system (dry conditions).
First inspect the circuit breaker. Move the circuit breakers into different locations in order to determine if the tripped condition will follow the circuit breaker. Check the wiring connection at the breaker. Remove the wires and reinstall the wires into the circuit breaker. Use low air pressure to clean the generator and the circuit breakers. Refer to Special Instruction, SEHS9124, "Cleaning and Drying of the Generator" which instructs proper cleaning of the generator on a regular basis. If the tripped condition does not follow the circuit breaker, then test the suspected element using the test in the section below. Review the wiring for shorts or for grounds. Also, review the wiring schematics for latest potential updates that are available.Condition: The screed does not heat to operating temperature and the circuit breakers have tripped (wet conditions).
The root cause may be due to the circuit breaker, shorts in the wiring, grounds in the wiring, shorts in the elements, or grounds in the elements. Determine if the elements were under water or if the elements are wet. Visually inspect the wiring connections and the wiring in the elements. Determine if moisture has entered the connectors or the connections at the elements. Dry the system in order to determine if the circuit breaker continues to trip. Move the circuit breakers into different locations in order to determine if the tripped condition will follow the circuit breaker. If the tripped condition does not follow the circuit breaker, then test the suspected element using the test in the section below. Dry the screed heating system in order to test the suspect element by unplugging the suspect element. Operate the system until the suspected heater element is dry. Connect the harness to the element. If you continue to have a tripped circuit breaker, test the heater elements as described below. If the circuit breaker trips cease. Inspect the wiring to the connectors and the connectors to the heater elements for any moisture that may have entered the system. Reseal the electrical connectors to the heater elements if signs of moisture are present.Procedure for Screeds with Single Four Pin Deutsch Connectors
Illustration 1 g01571225
(1) Connectors For the Outer heating Element
(2) Connectors For the Inner heating Element
(3) Outer Heating Element
(4) Inner Heating ElementEach of the four sections of the screed plate is assembled with an inner electric heating element (4) and an outer electric heating element (3). The Cat Electric Screed Control will output a diagnostic flash code in order to alert the operator when one or more of the electrical components in the heating system malfunctions. When a heating element is suspected to be malfunctioning, the following procedure should be performed.Reference: For more information on the diagnostic flash codes, refer to System Operation, "Electric Heat System" in this manual.TEST THE RESISTANCE OF THE HEATING ELEMENT.Table 1 lists the part numbers for the various heating elements and the expected electrical resistance values.
Table 1
Resistance Values of the
First inspect the circuit breaker. Move the circuit breakers into different locations in order to determine if the tripped condition will follow the circuit breaker. Check the wiring connection at the breaker. Remove the wires and reinstall the wires into the circuit breaker. Use low air pressure to clean the generator and the circuit breakers. Refer to Special Instruction, SEHS9124, "Cleaning and Drying of the Generator" which instructs proper cleaning of the generator on a regular basis. If the tripped condition does not follow the circuit breaker, then test the suspected element using the test in the section below. Review the wiring for shorts or for grounds. Also, review the wiring schematics for latest potential updates that are available.Condition: The screed does not heat to operating temperature and the circuit breakers have tripped (wet conditions).
The root cause may be due to the circuit breaker, shorts in the wiring, grounds in the wiring, shorts in the elements, or grounds in the elements. Determine if the elements were under water or if the elements are wet. Visually inspect the wiring connections and the wiring in the elements. Determine if moisture has entered the connectors or the connections at the elements. Dry the system in order to determine if the circuit breaker continues to trip. Move the circuit breakers into different locations in order to determine if the tripped condition will follow the circuit breaker. If the tripped condition does not follow the circuit breaker, then test the suspected element using the test in the section below. Dry the screed heating system in order to test the suspect element by unplugging the suspect element. Operate the system until the suspected heater element is dry. Connect the harness to the element. If you continue to have a tripped circuit breaker, test the heater elements as described below. If the circuit breaker trips cease. Inspect the wiring to the connectors and the connectors to the heater elements for any moisture that may have entered the system. Reseal the electrical connectors to the heater elements if signs of moisture are present.Procedure for Screeds with Single Four Pin Deutsch Connectors
Illustration 1 g01571225
(1) Connectors For the Outer heating Element
(2) Connectors For the Inner heating Element
(3) Outer Heating Element
(4) Inner Heating ElementEach of the four sections of the screed plate is assembled with an inner electric heating element (4) and an outer electric heating element (3). The Cat Electric Screed Control will output a diagnostic flash code in order to alert the operator when one or more of the electrical components in the heating system malfunctions. When a heating element is suspected to be malfunctioning, the following procedure should be performed.Reference: For more information on the diagnostic flash codes, refer to System Operation, "Electric Heat System" in this manual.TEST THE RESISTANCE OF THE HEATING ELEMENT.Table 1 lists the part numbers for the various heating elements and the expected electrical resistance values.
Table 1
Resistance Values of the
Caterpillar parts catalog:
Parts piston Caterpillar catalog:
7S4000
PISTON
824B, 825B, 834, 834B, 972G, 980G, 980G II, 988, 988B, 992, 992C, 992D, D44B, D550B
824B, 825B, 834, 834B, 972G, 980G, 980G II, 988, 988B, 992, 992C, 992D, D44B, D550B
8S5696
PISTON
834, 992
834, 992
8S4527
PISTON
824B, 834, 992
824B, 834, 992
7J3473
PISTON
992
992
7J1199
PISTON
992
992
7J9064
PISTON
992
992
7J8063
PISTON
992
992
8J0176
PISTON
992
992
8J5979
PISTON
992
992
8J3558
PISTON
992
992
1S8544
PISTON
769, 772, 834, 992
769, 772, 834, 992
9M4395
PISTON
769, 772, 834, 992
769, 772, 834, 992
8J5979
PISTON
992
992
8J0176
PISTON
992
992
6J9324
PISTON
966C
966C
4K2385
PISTON
950, 988
950, 988
1S8544
PISTON
769, 772, 834, 992
769, 772, 834, 992
1S0060
PISTON
988
988
4M1598
PISTON
988
988
9J4894
PISTON
988
988
8J3558
PISTON
992
992
8J2627
PISTON
950
950