Information:
Parameters
Illustration 2 g00352013
Press the temperature select switch (increase) (4) , the temperature select switch (decrease) (5) and the automatic temperature control switch (2) simultaneously. This will start the diagnostic mode. The automatic temperature control unit (ATC) will continue to function normally during the diagnostic mode. Parameters can be viewed on the control panel and parameters can be revised on the control panel. Sensor readings can also be viewed on the control panel.
Illustration 3 g00377432
Parameters are selected by using fan speed override switch (increase) (9) and fan speed override switch (decrease) (8) . For example, the parameter value "P01" will be briefly displayed. The current value of the setpoint will follow. Refer to table 2 for the list of parameters and a brief explanation of each parameter.
Push On/Off switch (1) once in order to return to the normal mode of operation.
Table 1
Parameter Value    Parameter Name    Explanation of Parameter    
"P00"     CONTROL MODULE SOFTWARE     Version number 1.3    
"P01"     DIRECT SUNLIGHT     A number between 10 and 20 will be displayed for no sunlight. A number between 200 and 250 will be displayed for full sunlight.    
"P02"     VALVE POSITION     A number from 0 to 15 indicates the position of the water valve. 0 is closed. 15 is fully open.    
"P03"     AIR TEMPERATURE IN THE CAB     The control panel displays temperatures in Degrees Celsius or in Degrees Fahrenheit.    
"P05"     EXTERNAL TEMPERATURE (ambient air)     The external ambient air temperature is displayed.    
"P07"     COOLANT TEMPERATURE (water)     This is used to limit the fan speed when the cab is cold and the engine coolant is cool.    
"P08"     TEMPERATURE AT EVAPORATOR COIL     This is used for freeze protection. The compressor is turned off when the temperature of the evaporator falls below the critical temperature (30° F).    
"P09"     TEMPERATURE DIFFERENCE     The air temperature in the cab minus the setpoint is displayed.    
"P10"     "COOL_ON"     The temperature above the setpoint that is required to turn ON the compressor is displayed.    
"P11"     "COOL_OFF"     The temperature below the setpoint that is required to turn OFF the compressor is displayed.    
"P12"     "FAN_MAX"     The temperature difference that is required to turn the blower to high speed is displayed.    
"P13"     "HEAT_MAX"     The temperature difference that is required to completely open the water valve is displayed.    
"P14"     SUN BIAS     The maximum temperature offset due to full sunlight is displayed.    
"P15"     EXTERNAL BIAS     The maximum temperature offset due to ambient air temperature is displayed.    
"P16"     COMPRESSOR BIAS     The temperature offset due to the compressor is displayed.    
"P18"     VALVE MINIMUM     This indicates the difference in potentiometer settings when the water valve is fully closed. This is determined by the ATC control module when the unit is first powered up. The typical value will be 0 to 20.    
"P19"     VALVE
Illustration 2 g00352013
Press the temperature select switch (increase) (4) , the temperature select switch (decrease) (5) and the automatic temperature control switch (2) simultaneously. This will start the diagnostic mode. The automatic temperature control unit (ATC) will continue to function normally during the diagnostic mode. Parameters can be viewed on the control panel and parameters can be revised on the control panel. Sensor readings can also be viewed on the control panel.
Illustration 3 g00377432
Parameters are selected by using fan speed override switch (increase) (9) and fan speed override switch (decrease) (8) . For example, the parameter value "P01" will be briefly displayed. The current value of the setpoint will follow. Refer to table 2 for the list of parameters and a brief explanation of each parameter.
Push On/Off switch (1) once in order to return to the normal mode of operation.
Table 1
Parameter Value    Parameter Name    Explanation of Parameter    
"P00"     CONTROL MODULE SOFTWARE     Version number 1.3    
"P01"     DIRECT SUNLIGHT     A number between 10 and 20 will be displayed for no sunlight. A number between 200 and 250 will be displayed for full sunlight.    
"P02"     VALVE POSITION     A number from 0 to 15 indicates the position of the water valve. 0 is closed. 15 is fully open.    
"P03"     AIR TEMPERATURE IN THE CAB     The control panel displays temperatures in Degrees Celsius or in Degrees Fahrenheit.    
"P05"     EXTERNAL TEMPERATURE (ambient air)     The external ambient air temperature is displayed.    
"P07"     COOLANT TEMPERATURE (water)     This is used to limit the fan speed when the cab is cold and the engine coolant is cool.    
"P08"     TEMPERATURE AT EVAPORATOR COIL     This is used for freeze protection. The compressor is turned off when the temperature of the evaporator falls below the critical temperature (30° F).    
"P09"     TEMPERATURE DIFFERENCE     The air temperature in the cab minus the setpoint is displayed.    
"P10"     "COOL_ON"     The temperature above the setpoint that is required to turn ON the compressor is displayed.    
"P11"     "COOL_OFF"     The temperature below the setpoint that is required to turn OFF the compressor is displayed.    
"P12"     "FAN_MAX"     The temperature difference that is required to turn the blower to high speed is displayed.    
"P13"     "HEAT_MAX"     The temperature difference that is required to completely open the water valve is displayed.    
"P14"     SUN BIAS     The maximum temperature offset due to full sunlight is displayed.    
"P15"     EXTERNAL BIAS     The maximum temperature offset due to ambient air temperature is displayed.    
"P16"     COMPRESSOR BIAS     The temperature offset due to the compressor is displayed.    
"P18"     VALVE MINIMUM     This indicates the difference in potentiometer settings when the water valve is fully closed. This is determined by the ATC control module when the unit is first powered up. The typical value will be 0 to 20.    
"P19"     VALVE
Parts plate Caterpillar catalog:
0909224
PLATE
Caterpillar
Caterpillar
0908979
PLATE
Caterpillar
Caterpillar
0908978
PLATE
Caterpillar
Caterpillar
0908798
PLATE
Caterpillar
Caterpillar
0908763
PLATE
Caterpillar
Caterpillar
0908745
PLATE
Caterpillar
Caterpillar
0909439
PLATE
Caterpillar
Caterpillar
0909393
PLATE A
Caterpillar
Caterpillar
0909358
PLATE
Caterpillar
Caterpillar
0909357
PLATE
Caterpillar
Caterpillar
0909325
PLATE
Caterpillar
Caterpillar
0909307
PLATE
Caterpillar
Caterpillar