3694837 PLUG-PIPE Caterpillar parts
Rating:
Alternative (cross code) number:
CA3694837
369-4837
3694837
CA3694837
369-4837
3694837
Weight: 0.09 pounds 0 kg.
Information:
Recommended Periodic Insulation Tests
The high voltage that is produced by an operating generator set can cause severe injury or death. Before performing any maintenance or repairs, ensure that the generator will not start.Place the engine control switch in the "OFF" position. Attach "DO NOT OPERATE" tags to all starting controls. Disconnect the batteries or disable the starting system. Lock out all switchgear and automatic transfer switches that are associated with the generator.
Table 1
Tools Needed
Part Number Part Name Quantity
300-8648 Insulation Testing Gp 1
Illustration 1 g01388839
PMPE Generator Wiring Diagram
(CR1-C6) Diodes
(CR7) Varistor
(L1) Exciter Stator
(L2) Exciter Rotor
(L3) Main Rotor
(L4) Main Stator
(L5) PMG Stator
(PM) Permanent Magnet
(RFA) Rotating Field Assembly
(CT1) Optional Voltage Droop Transformer
(T0, T1, T2, T3, T7, T8, T9) Generator terminals
Periodically, use an insulation tester to check the insulation resistance of the generators main stator winding. The frequency of this test is determined by the generators environment. Previous insulation tester readings will also determine the frequency of this test.Test the main stator windings with an insulation tester in the following situations:
The generator set is started for the first time.
The generator set is removed from storage.
The generator set is operating in a humid environment. Test every 3 months.
The generator set is not protected from the elements in an enclosed area. Test every 3 months.
The generator set is installed in an enclosed area. This area needs to be low in humidity and this area needs to have steady temperatures. Test every 12 months (minimum).
The generator set has not been run under load for 3 months. Test the generator set weekly. Use space heaters around the generator set if the generator is exposed to a sea water environment or if the humidity is above 75 percent. Also use space heaters if a test result was below 3 megohms.Space heaters must be used whenever the generator set is not under load. Space heaters must be used whenever salt is present or high humidity is present. Using a space heater in this fashion is the only way to maintain insulation tester readings above 1 megohm. Use space heaters only when the generator is not running.For additional information, refer to Special Instruction, SEHS9124, "Cleaning and Drying of Electric Set Generators".Recommended Procedure for the Insulation Test
Personal injury or death can result from electrocution.The megohmmeter is applying a high voltage to the circuit.To avoid electrocution, do not touch the instrument leads without first discharging them. When finished testing also discharge the generator windings.
Take the generator out of service.
Visually inspect the generator for moisture. If moisture exists, do not perform this insulation test. Dry the unit first. Refer to Special Instruction, SEHS9124, "Cleaning and Drying of Electric Set Generators".
Inspect the installation. Determine the equipment that will be tested by the insulation tester.
Discharge the capacitance of the windings.
Disconnect "T0" from ground.
Disconnect the sensing lead wires for the regulator. This may be accomplished by unplugging the harness connectors.
Disconnect the PT leads of the load share module.
Connect the insulation testers Black lead to ground.
Connect the insulation testers RED lead to "T0".
Set the voltage to the
The high voltage that is produced by an operating generator set can cause severe injury or death. Before performing any maintenance or repairs, ensure that the generator will not start.Place the engine control switch in the "OFF" position. Attach "DO NOT OPERATE" tags to all starting controls. Disconnect the batteries or disable the starting system. Lock out all switchgear and automatic transfer switches that are associated with the generator.
Table 1
Tools Needed
Part Number Part Name Quantity
300-8648 Insulation Testing Gp 1
Illustration 1 g01388839
PMPE Generator Wiring Diagram
(CR1-C6) Diodes
(CR7) Varistor
(L1) Exciter Stator
(L2) Exciter Rotor
(L3) Main Rotor
(L4) Main Stator
(L5) PMG Stator
(PM) Permanent Magnet
(RFA) Rotating Field Assembly
(CT1) Optional Voltage Droop Transformer
(T0, T1, T2, T3, T7, T8, T9) Generator terminals
Periodically, use an insulation tester to check the insulation resistance of the generators main stator winding. The frequency of this test is determined by the generators environment. Previous insulation tester readings will also determine the frequency of this test.Test the main stator windings with an insulation tester in the following situations:
The generator set is started for the first time.
The generator set is removed from storage.
The generator set is operating in a humid environment. Test every 3 months.
The generator set is not protected from the elements in an enclosed area. Test every 3 months.
The generator set is installed in an enclosed area. This area needs to be low in humidity and this area needs to have steady temperatures. Test every 12 months (minimum).
The generator set has not been run under load for 3 months. Test the generator set weekly. Use space heaters around the generator set if the generator is exposed to a sea water environment or if the humidity is above 75 percent. Also use space heaters if a test result was below 3 megohms.Space heaters must be used whenever the generator set is not under load. Space heaters must be used whenever salt is present or high humidity is present. Using a space heater in this fashion is the only way to maintain insulation tester readings above 1 megohm. Use space heaters only when the generator is not running.For additional information, refer to Special Instruction, SEHS9124, "Cleaning and Drying of Electric Set Generators".Recommended Procedure for the Insulation Test
Personal injury or death can result from electrocution.The megohmmeter is applying a high voltage to the circuit.To avoid electrocution, do not touch the instrument leads without first discharging them. When finished testing also discharge the generator windings.
Take the generator out of service.
Visually inspect the generator for moisture. If moisture exists, do not perform this insulation test. Dry the unit first. Refer to Special Instruction, SEHS9124, "Cleaning and Drying of Electric Set Generators".
Inspect the installation. Determine the equipment that will be tested by the insulation tester.
Discharge the capacitance of the windings.
Disconnect "T0" from ground.
Disconnect the sensing lead wires for the regulator. This may be accomplished by unplugging the harness connectors.
Disconnect the PT leads of the load share module.
Connect the insulation testers Black lead to ground.
Connect the insulation testers RED lead to "T0".
Set the voltage to the
Parts plug Caterpillar catalog:
3687601
PLUG-SPL PIPE
Caterpillar
Caterpillar
3687586
PLUG-
Caterpillar
Caterpillar
3687407
PLUG-MAGNETIC
Caterpillar
Caterpillar
3687320
PLUG-SPECIAL
Caterpillar
Caterpillar
3687202
PLUG-CARR DIFF
Caterpillar
Caterpillar
3687151
PLUG-AXLE FILL
Caterpillar
Caterpillar
3699943
PLUG AS-CONN
Caterpillar
Caterpillar
3696882
PLUG AS-
Caterpillar
Caterpillar
3694954
PLUG
Caterpillar
Caterpillar
3694915
PLUG-SPECIAL
Caterpillar
Caterpillar
3694886
PLUG-EXPANSION
Caterpillar
Caterpillar
3694862
PLUG
Caterpillar
Caterpillar