Thermostatic Expansion Valve System
Illustration 1 g01077014
Many earlier model machines are equipped with the thermostatic expansion valve system. The following information explains the purpose of the thermostatic expansion valve:
Restrict refrigerant flow and allow the compressor to increase the pressure on the high side of the air conditioning system.
Control the amount of refrigerant that enters the evaporator.The part of the air conditioning system from the compressor outlet to the expansion valve inlet is called the high side. The thermostatic expansion valve causes a restriction to refrigerant flow that increases the pressure between the expansion valve (restriction) and the compressor. The increase in pressure allows the refrigerant to change from a gas to a liquid.The compressor increases the temperature of the refrigerant by concentrating the refrigerant into a smaller space. The expansion valve decreases the temperature, by allowing the refrigerant to spread out as the refrigerant leaves the orifice in the expansion valve. Because the pressure is greatly decreased, the refrigerant is coldest as the refrigerant leaves the expansion valve and enters the evaporator. The part of the air conditioning system from the expansion valve outlet to the compressor inlet is called the low side.The thermostatic expansion valve system is equipped with a receiver-dryer.Thermostatic Expansion Valve
Illustration 2 g01077017
Two types of expansion valves are used on machines: internally equalized and externally equalized. Both the internally equalized expansion valve and the externally equalized expansion valve have a thermal bulb that is connected to a diaphragm by a small tube. The thermal bulb contains a refrigerant. A clamp holds the thermal bulb securely to the evaporator exhaust line. The thermal bulb is sensitive to exhaust temperature. If the exhaust temperature increases, the refrigerant inside the bulb expands. The expanding refrigerant exerts pressure against the diaphragm in the top of the valve. The diaphragm is connected through a pin to the valve seat. Pressure that is exerted against the diaphragm causes the diaphragm pin and valve seat to move. As the valve seat moves away from the orifice, more refrigerant flows into the evaporator. An increase in the flow of refrigerant causes the evaporator exhaust to become cooler. The cooler exhaust temperature causes the refrigerant to condense in the thermal bulb. This reduces the pressure that is against the diaphragm, the pin, and the valve seat. The valve seat moves in order to reduce flow through the orifice.In the internally equalized valve, the pressure of the refrigerant that enters the evaporator is fed to the bottom of the diaphragm through the internal equalizing passage. Gas expansion in the thermal bulb must overcome the internal balancing pressure and the spring before the valve will open in order to increase refrigerant flow.On the external equalizer valve, the pressure that is fed to the bottom of the diaphragm is taken from the evaporator exhaust line by an equalizer tube. The equalizer tube balances the evaporator exhaust pressure against the pressure that is caused by the expansion of the gas in the thermal bulb.The superheat spring prevents surges of excessive
Illustration 1 g01077014
Many earlier model machines are equipped with the thermostatic expansion valve system. The following information explains the purpose of the thermostatic expansion valve:
Restrict refrigerant flow and allow the compressor to increase the pressure on the high side of the air conditioning system.
Control the amount of refrigerant that enters the evaporator.The part of the air conditioning system from the compressor outlet to the expansion valve inlet is called the high side. The thermostatic expansion valve causes a restriction to refrigerant flow that increases the pressure between the expansion valve (restriction) and the compressor. The increase in pressure allows the refrigerant to change from a gas to a liquid.The compressor increases the temperature of the refrigerant by concentrating the refrigerant into a smaller space. The expansion valve decreases the temperature, by allowing the refrigerant to spread out as the refrigerant leaves the orifice in the expansion valve. Because the pressure is greatly decreased, the refrigerant is coldest as the refrigerant leaves the expansion valve and enters the evaporator. The part of the air conditioning system from the expansion valve outlet to the compressor inlet is called the low side.The thermostatic expansion valve system is equipped with a receiver-dryer.Thermostatic Expansion Valve
Illustration 2 g01077017
Two types of expansion valves are used on machines: internally equalized and externally equalized. Both the internally equalized expansion valve and the externally equalized expansion valve have a thermal bulb that is connected to a diaphragm by a small tube. The thermal bulb contains a refrigerant. A clamp holds the thermal bulb securely to the evaporator exhaust line. The thermal bulb is sensitive to exhaust temperature. If the exhaust temperature increases, the refrigerant inside the bulb expands. The expanding refrigerant exerts pressure against the diaphragm in the top of the valve. The diaphragm is connected through a pin to the valve seat. Pressure that is exerted against the diaphragm causes the diaphragm pin and valve seat to move. As the valve seat moves away from the orifice, more refrigerant flows into the evaporator. An increase in the flow of refrigerant causes the evaporator exhaust to become cooler. The cooler exhaust temperature causes the refrigerant to condense in the thermal bulb. This reduces the pressure that is against the diaphragm, the pin, and the valve seat. The valve seat moves in order to reduce flow through the orifice.In the internally equalized valve, the pressure of the refrigerant that enters the evaporator is fed to the bottom of the diaphragm through the internal equalizing passage. Gas expansion in the thermal bulb must overcome the internal balancing pressure and the spring before the valve will open in order to increase refrigerant flow.On the external equalizer valve, the pressure that is fed to the bottom of the diaphragm is taken from the evaporator exhaust line by an equalizer tube. The equalizer tube balances the evaporator exhaust pressure against the pressure that is caused by the expansion of the gas in the thermal bulb.The superheat spring prevents surges of excessive
Parts screen Caterpillar catalog:
9B7914
SCREEN
Caterpillar
Caterpillar
9B7668
SCREEN
Caterpillar
Caterpillar
9B7482
SCREEN A.
Caterpillar
Caterpillar
9B4823
SCREEN
Caterpillar
Caterpillar
9B4546
SCREEN A.
Caterpillar
Caterpillar
9B3834
SCREEN A.
Caterpillar
Caterpillar
9B8772
SCREEN A
Caterpillar
Caterpillar
9B8771
SCREEN
Caterpillar
Caterpillar
9B8728
SCREEN A
Caterpillar
Caterpillar
9B8727
SCREEN A.
Caterpillar
Caterpillar
9B8694
SCREEN &
Caterpillar
Caterpillar
9B8094
SCREEN
Caterpillar
Caterpillar