9V3131 SEAL-PISTON Caterpillar parts
69D, 769C, 769D, 771C, 771D, 772B, 773B, 773D, 773E, 775B, 775D, 775E, 776C, 776D, 777B, 777D, 784B, 784C, 785B, 785C, 785D, 789B, 789C, 789D, 793B, 793C, 793D, D25C, D25D, D30C, D350C, D400, D40D, D4...
Rating:
Alternative (cross code) number:
CA9V3131
9V-3131
9V3131
CA9V3131
9V-3131
9V3131
Weight: 0.30 pounds 0 kg.
ARTICULATED TRUCK, TRUCK,
Compatible equipment models: 9V3131:
Information:
Lead Numbering
The Wye (Star) configurations and the Delta configurations are the most common generator lead connections. The following three-phase connection diagrams illustrate the proper connection and lead identification.The leads are numbered clockwise from the top and from the outside inward. The diagrams show lead numbering for the six and twelve lead generators.Wye Configuration Diagrams
6 Lead
Illustration 1 g03839989
6 Lead Wye Configuration
Terminals T4, T5, and T6 become neutral connection when the terminals are tied together.
12 Lead
Illustration 2 g03840008
12 Lead Wye Configuration - High Voltage
Terminals T10, T11, and T12 become neutral connection when the terminals are tied together.
Illustration 3 g03840056
12 Lead Wye Configuration - Low Voltage
Terminals T10, T11, and T12 become neutral connection when the terminals are tied together.
Delta Configuration Diagrams
6 Lead
Illustration 4 g03840105
6 Lead Delta Configuration
12 Lead
Illustration 5 g03840209
12 Lead Delta Configuration
Terminals T6 and T9 become the neutral connection when the terminals are tied together and grounded. This reflects the terminal T2 and T10 connection as the high phase.
Grounding the Frame
In any generator set installation, the frame of the generator must be positively connected to an earth ground. This connection is the first one that is made at the installation. This connection is the last one that should be removed. The ground connection must be flexible in order to avoid possible breakage in later operation.Ground connection cable or straps should have at least the current carrying capacity of the largest line lead to the connected load. Joints in cables or straps must be clean, free of electrical resistance, and protected from possible oxidation. Bolted ground connection joints eventually oxidize. The joints are frequent sources of radio frequency interference (RFI). Silver soldered and bolted joints are electrically and mechanically sound.Neutral Connections
The generators with grounded configuration usually have the neutral grounded when the generator is installed. However, there are some cases when definite measures can be taken in order to prevent ground faults on the load side. The purpose of the grounding of the neutral is to prevent load side equipment damage. The purpose of the grounding of the neutral is also to prevent harm to personnel.If the neutral wire is grounded and one of the phase leads becomes grounded, the excessive current will open a load circuit breaker in order to isolate the fault. The excessive current will collapse the generator voltage, if the circuit breaker does not trip first. The result depends on the particular generator electrical characteristics, type of fault and trip rating of the circuit breaker. An undervoltage device may be required in order to provide an adequate short circuit protection.In some instances it is undesirable to ground the neutral wire. An ungrounded generator neutral lead is acceptable in the applications in which definite measures have been taken in order to prevent grounds to the phase leads. An example of such measures are ground fault protective circuits. Ground fault protection requires that the entire group of distribution circuits should be studied and treated as a system.
The Wye (Star) configurations and the Delta configurations are the most common generator lead connections. The following three-phase connection diagrams illustrate the proper connection and lead identification.The leads are numbered clockwise from the top and from the outside inward. The diagrams show lead numbering for the six and twelve lead generators.Wye Configuration Diagrams
6 Lead
Illustration 1 g03839989
6 Lead Wye Configuration
Terminals T4, T5, and T6 become neutral connection when the terminals are tied together.
12 Lead
Illustration 2 g03840008
12 Lead Wye Configuration - High Voltage
Terminals T10, T11, and T12 become neutral connection when the terminals are tied together.
Illustration 3 g03840056
12 Lead Wye Configuration - Low Voltage
Terminals T10, T11, and T12 become neutral connection when the terminals are tied together.
Delta Configuration Diagrams
6 Lead
Illustration 4 g03840105
6 Lead Delta Configuration
12 Lead
Illustration 5 g03840209
12 Lead Delta Configuration
Terminals T6 and T9 become the neutral connection when the terminals are tied together and grounded. This reflects the terminal T2 and T10 connection as the high phase.
Grounding the Frame
In any generator set installation, the frame of the generator must be positively connected to an earth ground. This connection is the first one that is made at the installation. This connection is the last one that should be removed. The ground connection must be flexible in order to avoid possible breakage in later operation.Ground connection cable or straps should have at least the current carrying capacity of the largest line lead to the connected load. Joints in cables or straps must be clean, free of electrical resistance, and protected from possible oxidation. Bolted ground connection joints eventually oxidize. The joints are frequent sources of radio frequency interference (RFI). Silver soldered and bolted joints are electrically and mechanically sound.Neutral Connections
The generators with grounded configuration usually have the neutral grounded when the generator is installed. However, there are some cases when definite measures can be taken in order to prevent ground faults on the load side. The purpose of the grounding of the neutral is to prevent load side equipment damage. The purpose of the grounding of the neutral is also to prevent harm to personnel.If the neutral wire is grounded and one of the phase leads becomes grounded, the excessive current will open a load circuit breaker in order to isolate the fault. The excessive current will collapse the generator voltage, if the circuit breaker does not trip first. The result depends on the particular generator electrical characteristics, type of fault and trip rating of the circuit breaker. An undervoltage device may be required in order to provide an adequate short circuit protection.In some instances it is undesirable to ground the neutral wire. An ungrounded generator neutral lead is acceptable in the applications in which definite measures have been taken in order to prevent grounds to the phase leads. An example of such measures are ground fault protective circuits. Ground fault protection requires that the entire group of distribution circuits should be studied and treated as a system.
Cat SIS web machinery list:
Parts seal Caterpillar catalog:
9J5570
SEAL
777D, 777F
777D, 777F
1T0352
SEAL
16, 768B, 769, 769C, 772, 773, 773B, D35HP, D400
16, 768B, 769, 769C, 772, 773, 773B, D35HP, D400
8J3879
SEAL
769, 772, 773B, 777
769, 772, 773B, 777
9J1797
SEAL
769, 772, 773B, 776, 777
769, 772, 773B, 776, 777
9J1794
SEAL
769, 772, 773B, 776, 777
769, 772, 773B, 776, 777
1S1115
SEAL
769C
769C
9H2257
SEAL
120B, 12E, 140, 140B, 769, 769C, 824
120B, 12E, 140, 140B, 769, 769C, 824
6V5607
SEAL-LIP TYPE
773B
773B
6V6804
SEAL-LIP TYPE
768C, 769C
768C, 769C
1166109
SEAL-LIP
773B
773B
2U5377
SEAL
D250B, D250D, D25C, D25D, D300B, D300D, D300E, D30C, D350C, D35C, D35HP, D400, D40D, D44B, D550B
D250B, D250D, D25C, D25D, D300B, D300D, D300E, D30C, D350C, D35C, D35HP, D400, D40D, D44B, D550B
6V2772
SEAL-O-RING
784B, 784C, 785, 785B, 785C, 785D, 789, 789B, 789C, 789D, 793, 793B, 793C, 793D, 793F, 793F CMD, 793F OEM, 793F-XQ
784B, 784C, 785, 785B, 785C, 785D, 789, 789B, 789C, 789D, 793, 793B, 793C, 793D, 793F, 793F CMD, 793F OEM, 793F-XQ
6V2656
SEAL-RING
777G, 784B, 784C, 785, 785B, 785C, 785D, 789, 789B, 789C, 789D, 793, 793B, 793C, 793D, 793F, 793F CMD, 793F OEM, 793F-XQ, AD55, AD55B, AD60
777G, 784B, 784C, 785, 785B, 785C, 785D, 789, 789B, 789C, 789D, 793, 793B, 793C, 793D, 793F, 793F CMD, 793F OEM, 793F-XQ, AD55, AD55B, AD60
1237269
SEAL-RING
777G, 784B, 784C, 785, 785B, 785C, 785D, 789, 789B, 789C, 789D, 793, 793B, 793C, 793D, 793F, 793F CMD, 793F OEM, 793F-XQ, AD55, AD55B, AD60
777G, 784B, 784C, 785, 785B, 785C, 785D, 789, 789B, 789C, 789D, 793, 793B, 793C, 793D, 793F, 793F CMD, 793F OEM, 793F-XQ, AD55, AD55B, AD60
6V2658
SEAL-RING
784B, 784C, 785, 785B, 785C, 785D, 789, 789B, 789C, 789D, 793, 793B, 793C, 793D, 793F, 793F CMD, 793F OEM, 793F-XQ
784B, 784C, 785, 785B, 785C, 785D, 789, 789B, 789C, 789D, 793, 793B, 793C, 793D, 793F, 793F CMD, 793F OEM, 793F-XQ
1237273
SEAL-RING
784B, 784C, 785, 785B, 785C, 785D, 789, 789B, 789C, 789D, 793, 793B, 793C, 793D, 793F, 793F AC, 793F CMD, 793F OEM, 793F-XQ
784B, 784C, 785, 785B, 785C, 785D, 789, 789B, 789C, 789D, 793, 793B, 793C, 793D, 793F, 793F AC, 793F CMD, 793F OEM, 793F-XQ
9D7984
SEAL
24H, 69D, 768C, 769C, 769D, 770, 771C, 771D, 772, 772B, 773B, 773D, 773F, 775B, 775D, 775F, 776C, 776D, 777, 777B, 777D, 784B, 784C, 785, 785B, 785C, 789, 789B, 789C, 793, 793B, 793C, 797, 797B, AD40,...
24H, 69D, 768C, 769C, 769D, 770, 771C, 771D, 772, 772B, 773B, 773D, 773F, 775B, 775D, 775F, 776C, 776D, 777, 777B, 777D, 784B, 784C, 785, 785B, 785C, 789, 789B, 789C, 793, 793B, 793C, 797, 797B, AD40,...
6E0253
SEAL AS
793, 793B, 793C
793, 793B, 793C
9T4059
SEAL-O-RING
789, 789B, 789C, 789D, 793, 793B, 793C, 793D, 793F, 793F AC, 793F CMD, 793F OEM, 793F-XQ, 795F AC, 795F XQ, 797, 797B, 797F
789, 789B, 789C, 789D, 793, 793B, 793C, 793D, 793F, 793F AC, 793F CMD, 793F OEM, 793F-XQ, 795F AC, 795F XQ, 797, 797B, 797F
9T4018
SEAL
789, 789B, 789C, 789D, 793, 793B, 793C, 793D, 793F, 793F AC, 793F CMD, 793F OEM, 793F-XQ
789, 789B, 789C, 789D, 793, 793B, 793C, 793D, 793F, 793F AC, 793F CMD, 793F OEM, 793F-XQ
1491488
SEAL-LIP TYPE
793C, 793D, D250D
793C, 793D, D250D
1485674
SEAL-BUFFER
793C, 793D
793C, 793D
1387131
SEAL
69D, 769C, 769D, 771C, 771D, 773B, 773D, 773E, 775B, 775D, 775E, 776C, 776D, 777D, 784B, 784C, 785B, 785C, 785D, 789B, 789C, 789D, 793B, 793C, 793D
69D, 769C, 769D, 771C, 771D, 773B, 773D, 773E, 775B, 775D, 775E, 776C, 776D, 777D, 784B, 784C, 785B, 785C, 785D, 789B, 789C, 789D, 793B, 793C, 793D