3354438 SEAT AR Caterpillar parts
Rating:
Alternative (cross code) number:
CA3354438
335-4438
3354438
CA3354438
335-4438
3354438
Weight: 180 pounds 81 kg.
Compare Prices:
As an associate, we earn commssions on qualifying purchases through the links below
Caterpillar SIS machinery equipment:
Caterpillar parts catalog:
Information:
to separate signal and power grounds by providing non chassis return for power distribution.Ground Loops
Ground loops can occur from two sources of noise:* Ground potentials* Electromagnetic fieldsThe previous section covered how ground potentials occur. Figure C-4 illustrates how a ground potential can cause interference to an electronic control system.
Figure C-4. Common Ground Impedance CouplingGround current IG, creates the ground potential VG, through the common ground impedance, ZG. This potential drives current through the loop formed by the source and load wiring. This current creates an error voltage across the load impedance.In a load sharing system, load imbalance is a result of dc ground potentials. Load sharing instability or slow system response are a result of ac ground potentials. Provide separate ground returns for electronic devices.Electromagnetic fields also can induce current into a loop. Figure C-5 shows a ground loop formed by signal leads and circuit common. The field flux cuts through the loop and induces current flow. (This is the same principle that applies to generators.) The resulting voltage across the load causes an error in the measurement.
Figure C-5. Ground Loop Coupling from and Electromagnetic FieldThe current induced into a loop is proportional to the field strength and area of the loop. Reducing field strength and loop area are both effective reduction methods. Loop area can be reduced by locating the electronics closer together and routing interconnecting wires near signal ground. Field strength can be reduced by routing wires as far from field sources as possible and orienting wiring at right angles to field sources. Shielding can be placed between the field source and wires to reduce the flux reaching the loop. This will be covered in the shielding section.The most effective (and most expensive) solution to interference from ground loops is to open them. Figure C-6 shows the source floating with respect to ground, so no loop is formed as in Figures C-4 and C-5.
Figure C-6. No Ground Loop Coupling with Circuit Grounded at One End OnlyGround loops may be broken with isolated power supplies on the source or receiving circuits. For process signals such as 4-20mA or 1-5 V, loop isolators are available. Take care in such wiring to prevent ground of isolated circuits, usually via shields, which defeats the ground loop isolation.Though not related to grounding, electromagnetic fields can also induce current into loops formed by signal lines as in Figure C-7.
Figure C-7. Differential Mode Coupling into Loop Formed by Signal Lead PairLoop area and field strength reduction are again effective methods of reducing interference. Loop area is reduced by using twisted pairs and minimizing the area at terminations. Twisted pairs also offer a cancellation effect on low frequency noise.Summary
A properly designed ground system is the most effective EMI control method at low frequencies. The design should consider using:* Signal ground for electronics separate from power and safety ground to prevent ground potentials.* Minimum loop areas to reduce electromagnetic field coupling.* Electronic wiring located as far as possible from sources of fields.* Elimination of ground
Ground loops can occur from two sources of noise:* Ground potentials* Electromagnetic fieldsThe previous section covered how ground potentials occur. Figure C-4 illustrates how a ground potential can cause interference to an electronic control system.
Figure C-4. Common Ground Impedance CouplingGround current IG, creates the ground potential VG, through the common ground impedance, ZG. This potential drives current through the loop formed by the source and load wiring. This current creates an error voltage across the load impedance.In a load sharing system, load imbalance is a result of dc ground potentials. Load sharing instability or slow system response are a result of ac ground potentials. Provide separate ground returns for electronic devices.Electromagnetic fields also can induce current into a loop. Figure C-5 shows a ground loop formed by signal leads and circuit common. The field flux cuts through the loop and induces current flow. (This is the same principle that applies to generators.) The resulting voltage across the load causes an error in the measurement.
Figure C-5. Ground Loop Coupling from and Electromagnetic FieldThe current induced into a loop is proportional to the field strength and area of the loop. Reducing field strength and loop area are both effective reduction methods. Loop area can be reduced by locating the electronics closer together and routing interconnecting wires near signal ground. Field strength can be reduced by routing wires as far from field sources as possible and orienting wiring at right angles to field sources. Shielding can be placed between the field source and wires to reduce the flux reaching the loop. This will be covered in the shielding section.The most effective (and most expensive) solution to interference from ground loops is to open them. Figure C-6 shows the source floating with respect to ground, so no loop is formed as in Figures C-4 and C-5.
Figure C-6. No Ground Loop Coupling with Circuit Grounded at One End OnlyGround loops may be broken with isolated power supplies on the source or receiving circuits. For process signals such as 4-20mA or 1-5 V, loop isolators are available. Take care in such wiring to prevent ground of isolated circuits, usually via shields, which defeats the ground loop isolation.Though not related to grounding, electromagnetic fields can also induce current into loops formed by signal lines as in Figure C-7.
Figure C-7. Differential Mode Coupling into Loop Formed by Signal Lead PairLoop area and field strength reduction are again effective methods of reducing interference. Loop area is reduced by using twisted pairs and minimizing the area at terminations. Twisted pairs also offer a cancellation effect on low frequency noise.Summary
A properly designed ground system is the most effective EMI control method at low frequencies. The design should consider using:* Signal ground for electronics separate from power and safety ground to prevent ground potentials.* Minimum loop areas to reduce electromagnetic field coupling.* Electronic wiring located as far as possible from sources of fields.* Elimination of ground
Parts seat Caterpillar catalog:
9G9931
SEAT GP-SUSPENSION
D4E, D5B, D6D
D4E, D5B, D6D
2198094
SEAT GP-SUSPENSION
950G II, 950H, 962G II, 962H, 966G II, 966H, 972G II, 972H, 980G II, 980H, IT62H
950G II, 950H, 962G II, 962H, 966G II, 966H, 972G II, 972H, 980G II, 980H, IT62H
8Y4004
SEAT GP-STATIC
120G, 12G, 130G, 140G, 160G, 930R
120G, 12G, 130G, 140G, 160G, 930R
3456045
SEAT & MOUNTING GP
236D, 242D, 246D, 257D, 259D, 262D, 272D, 277D, 279D, 287D, 289D, 299D
236D, 242D, 246D, 257D, 259D, 262D, 272D, 277D, 279D, 287D, 289D, 299D
6A5610
SEAT ASSEMBLY
920, 930
920, 930
8V1176
SEAT GP
916, 926, 926A, 936, CS-643, D5H, G936, IT18, IT28
916, 926, 926A, 936, CS-643, D5H, G936, IT18, IT28
3095350
SEAT & MOUNTING GP
770G, 770G OEM, 772G, 772G OEM, 773F, 773G, 773G LRC, 773G OEM, 775F, 775G, 775G LRC, 775G OEM, 777F, 777G
770G, 770G OEM, 772G, 772G OEM, 773F, 773G, 773G LRC, 773G OEM, 775F, 775G, 775G LRC, 775G OEM, 777F, 777G
2405057
SEAT GP-SUSPENSION
311D LRR, 320D, 320D LRR, 324D, 325D L, 329D L, 330D L, 336D
311D LRR, 320D, 320D LRR, 324D, 325D L, 329D L, 330D L, 336D
8Y5481
SEAT GP
931C II, 935C II, D3C II, D4C II, D5C
931C II, 935C II, D3C II, D4C II, D5C
8Y5480
SEAT GP-ADJUSTABLE
931C II, 935C II, D3C II, D4C II, D5C
931C II, 935C II, D3C II, D4C II, D5C
8Y5042
SEAT & SUPPORT GP
D3C II
D3C II
2487511
SEAT GP-COMPANION
844H, 844K, 854K, 990H, 990K, 992K, 993K, 994F, 994H
844H, 844K, 854K, 990H, 990K, 992K, 993K, 994F, 994H