3904791 SFWR GP-A4012 Caterpillar parts SFWR
Rating:
Alternative (cross code) number:
CA3904791
390-4791
3904791
CA3904791
390-4791
3904791

Buy SFWR GP-A4012 3904791 Caterpillar genuine, new aftermarket tractor parts with delivery
Information:
Recommended Periodic Insulation Tests
The high voltage that is produced by an operating generator set can cause severe injury or death. Before performing any maintenance or repairs, ensure that the generator will not start.Place the engine control switch in the "OFF" position. Attach "DO NOT OPERATE" tags to all starting controls. Disconnect the batteries or disable the starting system. Lock out all switchgear and automatic transfer switches that are associated with the generator.
Periodically, use a megohmmeter to check the insulation resistance of the generator main stator winding. The frequency of this test is determined by the generator environment. Previous megohmmeter readings will also determine the frequency of this test.Test the main stator windings with a megohmmeter in the following situations:
The generator set is started for the first time.
The generator set is removed from storage.
The generator set is operating in a humid environment. Test every 3 months.
The generator set is not protected from the elements in an enclosed area. Test every 3 months.
The generator set is installed in an enclosed area. This area needs to be low in humidity and this area needs to have steady temperatures. Test every 12 months (minimum).
The generator set has not been run under load for 3 months. Test the generator set weekly. Use space heaters around the generator set if the generator is exposed to a sea water environment or if the humidity is above 75%. Also use space heaters if a test result was below 3 megohms.Space heaters must be used whenever the generator set is not under load. Space heaters must also be used whenever salt is present or whenever high humidity is present. Using a space heater in this fashion is the only way to maintain megohmmeter readings above 1 megohm. Use space heaters only when the generator is not running.For additional information, refer to Special Instruction, SEHS9124, "Cleaning and Drying of Electric Set Generators".Recommended Periodic Insulation Test Procedure
Personal injury or death can result from electrocution.The megohmmeter is applying a high voltage to the circuit.To avoid electrocution, do not touch the instrument leads without first discharging them. When finished testing also discharge the generator windings.
Take the generator out of service.
Visually inspect the generator for moisture. If moisture exists, do not perform this insulation test. Dry the unit first. Refer to Special Instruction, SEHS9124, "Cleaning and Drying of Electric Set Generators".
Inspect the installation. Determine the equipment that will be tested by the 9U-6003 Megohmmeter .
Discharge the capacitance of the windings.
Disconnect "T0" from ground.
Disconnect the regulator sensing lead wires: "20", "22" and "24".
Connect the megohmmeter RED lead to ground.
Connect the megohmmeter BLACK lead to "T0".
For units that are 600 V or less, set the voltage to 500 V. For units that are more than 600 V, set the voltage to 1000 V.
Use the 30/60 Time Resistance Method:
Apply voltage.
Observe the readings at 30 seconds. Observe the readings at 60 seconds.
Record the 60 second reading. This reading must be corrected for temperature.
Record temperature.
Record humidity.
Remove voltage.
Evaluate the readings. The actual value of the resistance may vary
The high voltage that is produced by an operating generator set can cause severe injury or death. Before performing any maintenance or repairs, ensure that the generator will not start.Place the engine control switch in the "OFF" position. Attach "DO NOT OPERATE" tags to all starting controls. Disconnect the batteries or disable the starting system. Lock out all switchgear and automatic transfer switches that are associated with the generator.
Periodically, use a megohmmeter to check the insulation resistance of the generator main stator winding. The frequency of this test is determined by the generator environment. Previous megohmmeter readings will also determine the frequency of this test.Test the main stator windings with a megohmmeter in the following situations:
The generator set is started for the first time.
The generator set is removed from storage.
The generator set is operating in a humid environment. Test every 3 months.
The generator set is not protected from the elements in an enclosed area. Test every 3 months.
The generator set is installed in an enclosed area. This area needs to be low in humidity and this area needs to have steady temperatures. Test every 12 months (minimum).
The generator set has not been run under load for 3 months. Test the generator set weekly. Use space heaters around the generator set if the generator is exposed to a sea water environment or if the humidity is above 75%. Also use space heaters if a test result was below 3 megohms.Space heaters must be used whenever the generator set is not under load. Space heaters must also be used whenever salt is present or whenever high humidity is present. Using a space heater in this fashion is the only way to maintain megohmmeter readings above 1 megohm. Use space heaters only when the generator is not running.For additional information, refer to Special Instruction, SEHS9124, "Cleaning and Drying of Electric Set Generators".Recommended Periodic Insulation Test Procedure
Personal injury or death can result from electrocution.The megohmmeter is applying a high voltage to the circuit.To avoid electrocution, do not touch the instrument leads without first discharging them. When finished testing also discharge the generator windings.
Take the generator out of service.
Visually inspect the generator for moisture. If moisture exists, do not perform this insulation test. Dry the unit first. Refer to Special Instruction, SEHS9124, "Cleaning and Drying of Electric Set Generators".
Inspect the installation. Determine the equipment that will be tested by the 9U-6003 Megohmmeter .
Discharge the capacitance of the windings.
Disconnect "T0" from ground.
Disconnect the regulator sensing lead wires: "20", "22" and "24".
Connect the megohmmeter RED lead to ground.
Connect the megohmmeter BLACK lead to "T0".
For units that are 600 V or less, set the voltage to 500 V. For units that are more than 600 V, set the voltage to 1000 V.
Use the 30/60 Time Resistance Method:
Apply voltage.
Observe the readings at 30 seconds. Observe the readings at 60 seconds.
Record the 60 second reading. This reading must be corrected for temperature.
Record temperature.
Record humidity.
Remove voltage.
Evaluate the readings. The actual value of the resistance may vary
Parts sfwr Caterpillar catalog:
3904790
SFWR GP-A4011
Caterpillar
Caterpillar
3904789
SFWR GP-A4011
Caterpillar
Caterpillar
3903825
SFWR GP-A6001
Caterpillar
Caterpillar
3901250
SFWR GP-A3000
Caterpillar
Caterpillar
3900444
SFWR GP-A5000
Caterpillar
Caterpillar
3900326
SFWR GP-A4001
Caterpillar
Caterpillar
3904792
SFWR GP-A4012
Caterpillar
Caterpillar
3908438
SFWR GP-A4008
Caterpillar
Caterpillar
3908439
SFWR GP-A4008
Caterpillar
Caterpillar
3908440
SFWR GP-A4008
Caterpillar
Caterpillar
3908441
SFWR GP-A4008
Caterpillar
Caterpillar
3908442
SFWR GP-A4008
Caterpillar
Caterpillar