5243185 SHOE-TRACK Caterpillar parts
Rating:
Alternative (cross code) number:
CA5243185
524-3185
5243185
CA5243185
524-3185
5243185
Weight: 60 pounds 27 kg.
Compare Prices: .
As an associate, we earn commssions on qualifying purchases through the links below
Information:
Recommended Periodic Insulation Tests
The high voltage that is produced by an operating generator set can cause severe injury or death. Before performing any maintenance or repairs, ensure that the generator will not start.Place the engine control switch in the "OFF" position. Attach "DO NOT OPERATE" tags to all starting controls. Disconnect the batteries or disable the starting system. Lock out all switchgear and automatic transfer switches that are associated with the generator.
Periodically, use a megohmmeter to check the insulation resistance of the generator main stator winding. The frequency of this test is determined by the generator environment. Previous megohmmeter readings will also determine the frequency of this test.Test the main stator windings with a megohmmeter in the following situations:
The generator set is started for the first time.
The generator set is removed from storage.
The generator set is operating in a humid environment. Test every 3 months.
The generator set is not protected from the elements in an enclosed area. Test every 3 months.
The generator set is installed in an enclosed area. This area needs to be low in humidity and this area needs to have steady temperatures. Test every 12 months (minimum).
The generator set has not been run under load for 3 months. Test the generator set weekly. Use space heaters around the generator set if the generator is exposed to a sea water environment or if the humidity is above 75%. Also use space heaters if a test result was below 3 megohms.Space heaters must be used whenever the generator set is not under load. Space heaters must also be used whenever salt is present or whenever high humidity is present. Using a space heater in this fashion is the only way to maintain megohmmeter readings above 1 megohm. Use space heaters only when the generator is not running.For additional information, refer to Special Instruction, SEHS9124, "Cleaning and Drying of Electric Set Generators".Recommended Periodic Insulation Test Procedure
Personal injury or death can result from electrocution.The megohmmeter is applying a high voltage to the circuit.To avoid electrocution, do not touch the instrument leads without first discharging them. When finished testing also discharge the generator windings.
Take the generator out of service.
Visually inspect the generator for moisture. If moisture exists, do not perform this insulation test. Dry the unit first. Refer to Special Instruction, SEHS9124, "Cleaning and Drying of Electric Set Generators".
Inspect the installation. Determine the equipment that will be tested by the 9U-6003 Megohmmeter .
Discharge the capacitance of the windings.
Disconnect "T0" from ground.
Disconnect the regulator sensing lead wires: "20", "22" and "24".
Connect the megohmmeter RED lead to ground.
Connect the megohmmeter BLACK lead to "T0".
For units that are 600 V or less, set the voltage to 500 V. For units that are more than 600 V, set the voltage to 1000 V.
Use the 30/60 Time Resistance Method:
Apply voltage.
Observe the readings at 30 seconds. Observe the readings at 60 seconds.
Record the 60 second reading. This reading must be corrected for temperature.
Record temperature.
Record humidity.
Remove voltage.
Evaluate the readings. The actual value of the resistance may vary
The high voltage that is produced by an operating generator set can cause severe injury or death. Before performing any maintenance or repairs, ensure that the generator will not start.Place the engine control switch in the "OFF" position. Attach "DO NOT OPERATE" tags to all starting controls. Disconnect the batteries or disable the starting system. Lock out all switchgear and automatic transfer switches that are associated with the generator.
Periodically, use a megohmmeter to check the insulation resistance of the generator main stator winding. The frequency of this test is determined by the generator environment. Previous megohmmeter readings will also determine the frequency of this test.Test the main stator windings with a megohmmeter in the following situations:
The generator set is started for the first time.
The generator set is removed from storage.
The generator set is operating in a humid environment. Test every 3 months.
The generator set is not protected from the elements in an enclosed area. Test every 3 months.
The generator set is installed in an enclosed area. This area needs to be low in humidity and this area needs to have steady temperatures. Test every 12 months (minimum).
The generator set has not been run under load for 3 months. Test the generator set weekly. Use space heaters around the generator set if the generator is exposed to a sea water environment or if the humidity is above 75%. Also use space heaters if a test result was below 3 megohms.Space heaters must be used whenever the generator set is not under load. Space heaters must also be used whenever salt is present or whenever high humidity is present. Using a space heater in this fashion is the only way to maintain megohmmeter readings above 1 megohm. Use space heaters only when the generator is not running.For additional information, refer to Special Instruction, SEHS9124, "Cleaning and Drying of Electric Set Generators".Recommended Periodic Insulation Test Procedure
Personal injury or death can result from electrocution.The megohmmeter is applying a high voltage to the circuit.To avoid electrocution, do not touch the instrument leads without first discharging them. When finished testing also discharge the generator windings.
Take the generator out of service.
Visually inspect the generator for moisture. If moisture exists, do not perform this insulation test. Dry the unit first. Refer to Special Instruction, SEHS9124, "Cleaning and Drying of Electric Set Generators".
Inspect the installation. Determine the equipment that will be tested by the 9U-6003 Megohmmeter .
Discharge the capacitance of the windings.
Disconnect "T0" from ground.
Disconnect the regulator sensing lead wires: "20", "22" and "24".
Connect the megohmmeter RED lead to ground.
Connect the megohmmeter BLACK lead to "T0".
For units that are 600 V or less, set the voltage to 500 V. For units that are more than 600 V, set the voltage to 1000 V.
Use the 30/60 Time Resistance Method:
Apply voltage.
Observe the readings at 30 seconds. Observe the readings at 60 seconds.
Record the 60 second reading. This reading must be corrected for temperature.
Record temperature.
Record humidity.
Remove voltage.
Evaluate the readings. The actual value of the resistance may vary
Caterpillar parts catalog:
Parts shoe Caterpillar catalog:
5243183
SHOE-TRACK
Caterpillar
Caterpillar
4993593
SHOE AS
Caterpillar
Caterpillar
4993592
SHOE AS
Caterpillar
Caterpillar
4993591
SHOE AS
Caterpillar
Caterpillar
4993590
SHOE AS
Caterpillar
Caterpillar
4902562
SHOE AS-CUTOFF
Caterpillar
Caterpillar
2227359
SHOE-TRACK
Caterpillar
Caterpillar
1Q4769
SHOE-TRACK
Caterpillar
Caterpillar
8I0503
SHOE AS-CUTOFF
Caterpillar
Caterpillar
7R0145
SHOE-TRACK MASTER
Caterpillar
Caterpillar
6S7124
SHOE-GROUSER TRACK
Caterpillar
Caterpillar
5E9604
SHOE-TRACK
Caterpillar
Caterpillar