Information:
Chokes
Chokes in the Front of the Cabinet
Illustration 16 g02076793
Chokes in the Back of the Cabinet
Illustration 17 g02076794
Fans
The following fans are used:45L - These fans are 120 mm (4.7 inch) in diameter and move 45 L of air per second.90L - These fans are 150 mm (5.9 inch) in diameter and move 90 L of air per second.60 kVA PFC and Inverter IGBT Fans
These fans are a type 45L.
Illustration 18 g02077074
120 kVA PFC and Inverter IGBT Fans
These fans are a type 90L.
Illustration 19 g02077076
Static Switch Fans
These fans are a type 45L.
Illustration 20 g02077079
(28) AC bypass SS fans that are monitoredNote: The 60 kVA UPS configuration uses three of the four available fans. The 120 kVA configuration uses four of the five available fans.Choke Fans
Illustration 21 g02077081
Fans are a type 90LThe 60 kVA UPS configuration uses all three of the fans. The 120 kVA configuration uses all three of the fans.Charger and Neutral Leg Fan
These fans are a type 90L.
Illustration 22 g02077082
The 60 kVA configuration uses a type 45L fan. The 120 kVA configuration uses a type 90L fan.Current Transformer and LEM Locations
Current LEMs for AC Normal
The current LEMs are located on the top of the SS AC Nomal/Battery power module. The LEM is a device that measures AC and DC current. The 60 kVA UPS uses the LEM 60 current transformer. The 120 kVA UPS uses the LEM 120 current transformer.
Illustration 23 g02078058
Current LEMs for the Inverter
The inverter LEMs are located above the output inverter AC capacitors. The 60 kVA UPS uses the LEM 60 current transformer. The 120 kVA UPS uses the LEM 120 current transformer.
Illustration 24 g02078060
Output Current Transformers
The same current transformers are used for the 60 kVA UPS and the 120 kVA UPS. The transformers are type 1000/1. The current transformers are located behind the terminal block panel.
Illustration 25 g02078062
Paralleling Current Transformers
The same current transformers are used for the 60 kVA UPS and the 120 kVA UPS. The current transformers are located right side of the cabinet next to the DC capacitors.
Illustration 26 g02078063
Chokes in the Front of the Cabinet
Illustration 16 g02076793
Chokes in the Back of the Cabinet
Illustration 17 g02076794
Fans
The following fans are used:45L - These fans are 120 mm (4.7 inch) in diameter and move 45 L of air per second.90L - These fans are 150 mm (5.9 inch) in diameter and move 90 L of air per second.60 kVA PFC and Inverter IGBT Fans
These fans are a type 45L.
Illustration 18 g02077074
120 kVA PFC and Inverter IGBT Fans
These fans are a type 90L.
Illustration 19 g02077076
Static Switch Fans
These fans are a type 45L.
Illustration 20 g02077079
(28) AC bypass SS fans that are monitoredNote: The 60 kVA UPS configuration uses three of the four available fans. The 120 kVA configuration uses four of the five available fans.Choke Fans
Illustration 21 g02077081
Fans are a type 90LThe 60 kVA UPS configuration uses all three of the fans. The 120 kVA configuration uses all three of the fans.Charger and Neutral Leg Fan
These fans are a type 90L.
Illustration 22 g02077082
The 60 kVA configuration uses a type 45L fan. The 120 kVA configuration uses a type 90L fan.Current Transformer and LEM Locations
Current LEMs for AC Normal
The current LEMs are located on the top of the SS AC Nomal/Battery power module. The LEM is a device that measures AC and DC current. The 60 kVA UPS uses the LEM 60 current transformer. The 120 kVA UPS uses the LEM 120 current transformer.
Illustration 23 g02078058
Current LEMs for the Inverter
The inverter LEMs are located above the output inverter AC capacitors. The 60 kVA UPS uses the LEM 60 current transformer. The 120 kVA UPS uses the LEM 120 current transformer.
Illustration 24 g02078060
Output Current Transformers
The same current transformers are used for the 60 kVA UPS and the 120 kVA UPS. The transformers are type 1000/1. The current transformers are located behind the terminal block panel.
Illustration 25 g02078062
Paralleling Current Transformers
The same current transformers are used for the 60 kVA UPS and the 120 kVA UPS. The current transformers are located right side of the cabinet next to the DC capacitors.
Illustration 26 g02078063
Caterpillar parts catalog:
Parts software Caterpillar catalog:
4551141
SOFTWARE GP-POWER TRAIN
Caterpillar
Caterpillar
4526111
SOFTWARE GP-POWER TRAIN
Caterpillar
Caterpillar
4502392
SOFTWARE GP-IMPLEMENT
Caterpillar
Caterpillar
4491729
SOFTWARE GP-POWER TRAIN
Caterpillar
Caterpillar
4437573
SOFTWARE GP-ENGINE
Caterpillar
Caterpillar
4373785
SOFTWARE GP-MONITOR
Caterpillar
Caterpillar
4782338
SOFTWARE GP-ENGINE
Caterpillar
Caterpillar
4770198
SOFTWARE GP-IMPLEMENT
Caterpillar
Caterpillar
4739695
SOFTWARE GP-MACHINE
Caterpillar
Caterpillar
4682813
SOFTWARE GP-POWER TRAIN
Caterpillar
Caterpillar
4667403
SOFTWARE GP-MONITOR
Caterpillar
Caterpillar
4640536
SOFTWARE GP-MONITOR
Caterpillar
Caterpillar