4547807 STEP AS Caterpillar parts
Rating:
Alternative (cross code) number:
CA4547807
454-7807
4547807
CA4547807
454-7807
4547807
Weight: 2 pounds 1 kg.
Information:
Loading of the Generator
When a generator is installed or reconnected, be sure that the total current in one phase does not exceed the nameplate rating. Each phase should carry the same load. The equal load allows the engine to work at the rated capacity. An electrical unbalance can result in an electrical overload and overheating if one phase current exceeds the nameplate amperage.Allowable combinations of unbalanced loads are shown in Illustration 1. When you operate with significant single-phase loads, the combinations of single-phase load and three-phase load may be used. Such combinations should be located below the line on the graph.
Illustration 1 g00627416
Allowable Combinations of Unbalanced LoadsBlock Loading
When an electrical load is applied to a generator set, block loading occurs. This load may be anywhere from a moderate percentage of the rated load up to the rated load.The block loading capability of a generator set depends on the following factors.
engine transient response
voltage regulator response
type of the voltage regulator
altitude of operation of the generator set
type of load
the amount of load that is already present If a block load derating is required, refer to ISO 8528 Standards or SAE J1349 Standards. Power Factor
The power factor represents the efficiency of the load. The power factor is the ratio of apparent power to total power. This ratio is expressed as a decimal. The power factor represents the portion of the current which is doing useful work. The portion of current which is not doing useful work is absorbed in maintaining the magnetic field in motors. This current is called the reactive load. Engine power is not required to maintain the reactive load.In most applications, electric motors, solid-state controls, and transformers determine the power factor of the system. Induction motors usually have a power factor that is no larger than 0.8. Incandescent lighting is a resistive load of about 1.0 power factor, or unity. Solid-state controls (motor starters), variable frequency drivers, variable speed drivers, and UPS systems can operate at any power factor, leading, or lagging. In this case, the power factor can be between 0.4 and 1.0.The power factor of a system may be determined by a power factor meter or by calculations. Determine the power requirement in kW by multiplying the power factor by the kVA that is supplied to the system. As the power factor increases, the total current that is supplied to a constant power demand will decrease. With equal loads, a lower power factor will draw more current. A high-power factor will result in full engine load that is less than the generator rated amperage. A lower power factor increases the possibility of overloading the generator.Note: Normally, Caterpillar generators are designed for a power factor of 0.8 lagging. Consult your Caterpillar dealer in order to check the generator rating if operation at less than 0.7 lagging power factor is desired.Excitation Systems
Permanent Magnet Pilot Excited Generators
Permanent Magnet Pilot Excited (PMPE) generators receive power for the voltage regulator from a pilot exciter, rather than the main armature. The pilot exciter consists
When a generator is installed or reconnected, be sure that the total current in one phase does not exceed the nameplate rating. Each phase should carry the same load. The equal load allows the engine to work at the rated capacity. An electrical unbalance can result in an electrical overload and overheating if one phase current exceeds the nameplate amperage.Allowable combinations of unbalanced loads are shown in Illustration 1. When you operate with significant single-phase loads, the combinations of single-phase load and three-phase load may be used. Such combinations should be located below the line on the graph.
Illustration 1 g00627416
Allowable Combinations of Unbalanced LoadsBlock Loading
When an electrical load is applied to a generator set, block loading occurs. This load may be anywhere from a moderate percentage of the rated load up to the rated load.The block loading capability of a generator set depends on the following factors.
engine transient response
voltage regulator response
type of the voltage regulator
altitude of operation of the generator set
type of load
the amount of load that is already present If a block load derating is required, refer to ISO 8528 Standards or SAE J1349 Standards. Power Factor
The power factor represents the efficiency of the load. The power factor is the ratio of apparent power to total power. This ratio is expressed as a decimal. The power factor represents the portion of the current which is doing useful work. The portion of current which is not doing useful work is absorbed in maintaining the magnetic field in motors. This current is called the reactive load. Engine power is not required to maintain the reactive load.In most applications, electric motors, solid-state controls, and transformers determine the power factor of the system. Induction motors usually have a power factor that is no larger than 0.8. Incandescent lighting is a resistive load of about 1.0 power factor, or unity. Solid-state controls (motor starters), variable frequency drivers, variable speed drivers, and UPS systems can operate at any power factor, leading, or lagging. In this case, the power factor can be between 0.4 and 1.0.The power factor of a system may be determined by a power factor meter or by calculations. Determine the power requirement in kW by multiplying the power factor by the kVA that is supplied to the system. As the power factor increases, the total current that is supplied to a constant power demand will decrease. With equal loads, a lower power factor will draw more current. A high-power factor will result in full engine load that is less than the generator rated amperage. A lower power factor increases the possibility of overloading the generator.Note: Normally, Caterpillar generators are designed for a power factor of 0.8 lagging. Consult your Caterpillar dealer in order to check the generator rating if operation at less than 0.7 lagging power factor is desired.Excitation Systems
Permanent Magnet Pilot Excited Generators
Permanent Magnet Pilot Excited (PMPE) generators receive power for the voltage regulator from a pilot exciter, rather than the main armature. The pilot exciter consists
Cat SIS web machinery list:
Parts step Caterpillar catalog:
5555707
STEP AS
Caterpillar
Caterpillar
5414603
STEP AS
Caterpillar
Caterpillar
5392790
STEP AS
Caterpillar
Caterpillar
5392785
STEP AS
Caterpillar
Caterpillar
5335579
STEP
Caterpillar
Caterpillar
5333256
STEP AS
Caterpillar
Caterpillar
0320995
STEP
Caterpillar
Caterpillar
0316363
STEP
Caterpillar
Caterpillar
0316362
STEP-RIGHT
Caterpillar
Caterpillar
4190881
STEP AS-YM
Caterpillar
Caterpillar
5010551
STEP AS-YM
Caterpillar
Caterpillar
4595070
STEP AS
Caterpillar
Caterpillar