GENERATOR SET,
Information:
System Operation Description:The following information must be known and recorded for paralleling operations. The information must be obtained at various load points. The information must match the generator readings.
Verify breaker outputs voltage
Current
Power
Power factor readingsThe following are what is expected:
Voltages are close to rated values
Readings from the EMCP and the CDVR match
No voltage exists on the output of the open breaker
Metering at various load points match the power analyzer readings
Metering at the output of breaker matches metering at input of breaker for paralleling
All power readings are positiveIf the expected data is not correct, then the following must be confirmed:
Confirm that the configuration is correct for the EMCP generator current transformers and the potential transformers.
Ensure that settings in the EMCP and the CDVR match
Check for correct wiring.
If negative kW is seen, check for correct CT polarityA non-adjustable and non-programmable shutdown immediately occurs when the generator breaker is closed and there is a generator sensing fault. This shutdown occurs when a phase difference (non-zero) between phase A on the generator and phase A on the bus is detected. An immediate shutdown test also occurs for the other phases.Test Step 1. Test Dead Bus Arbitration Wiring
Use a digital multimeter to verify continuity or voltages between the following points. Note: The generator set must be off.
Pin 24 on 70-pin/DBA-1 terminal
Pin 25 on 70-pin/DBA-2 terminal
Pin 6 on 70-pin/DBA-3 terminal
Pin 7 on 70-pin/DBA-4 terminal
Pin 26 on 70-pin/PIO-REF terminal
Verify battery voltage on the "Best Battery Positive Line" diode cathode.
Verify that 0 VDC exist across the DBA relay coil that is located in the terminal box.
If multiple generator sets are wired together, then verify the continuity between the following points.
DBA-1 terminals on all generator sets
DBA-2 terminals on all generator sets
DBA-3 terminals on all generator sets
DBA-4 terminals on all generator sets
PIO-REF terminals on all generator sets
Cathodes of the "Best Battery Positive Line" diodes on all generator setsExpected Result:The continuity or voltage exists between the test points.Results:
OK - The appropriate continuity or voltage exists between all of the test points.STOP
Not OK - The appropriate continuity or voltage does not exist between all of the test points.Repair: Repair the Wiring. Verify that the problem has been corrected. The generator set operates normally.STOP
Verify breaker outputs voltage
Current
Power
Power factor readingsThe following are what is expected:
Voltages are close to rated values
Readings from the EMCP and the CDVR match
No voltage exists on the output of the open breaker
Metering at various load points match the power analyzer readings
Metering at the output of breaker matches metering at input of breaker for paralleling
All power readings are positiveIf the expected data is not correct, then the following must be confirmed:
Confirm that the configuration is correct for the EMCP generator current transformers and the potential transformers.
Ensure that settings in the EMCP and the CDVR match
Check for correct wiring.
If negative kW is seen, check for correct CT polarityA non-adjustable and non-programmable shutdown immediately occurs when the generator breaker is closed and there is a generator sensing fault. This shutdown occurs when a phase difference (non-zero) between phase A on the generator and phase A on the bus is detected. An immediate shutdown test also occurs for the other phases.Test Step 1. Test Dead Bus Arbitration Wiring
Use a digital multimeter to verify continuity or voltages between the following points. Note: The generator set must be off.
Pin 24 on 70-pin/DBA-1 terminal
Pin 25 on 70-pin/DBA-2 terminal
Pin 6 on 70-pin/DBA-3 terminal
Pin 7 on 70-pin/DBA-4 terminal
Pin 26 on 70-pin/PIO-REF terminal
Verify battery voltage on the "Best Battery Positive Line" diode cathode.
Verify that 0 VDC exist across the DBA relay coil that is located in the terminal box.
If multiple generator sets are wired together, then verify the continuity between the following points.
DBA-1 terminals on all generator sets
DBA-2 terminals on all generator sets
DBA-3 terminals on all generator sets
DBA-4 terminals on all generator sets
PIO-REF terminals on all generator sets
Cathodes of the "Best Battery Positive Line" diodes on all generator setsExpected Result:The continuity or voltage exists between the test points.Results:
OK - The appropriate continuity or voltage exists between all of the test points.STOP
Not OK - The appropriate continuity or voltage does not exist between all of the test points.Repair: Repair the Wiring. Verify that the problem has been corrected. The generator set operates normally.STOP
Cat SIS web machinery list:
Parts support Caterpillar catalog:
2698242
SUPPORT
3013C, 3024C, C1.5, C2.2
3013C, 3024C, C1.5, C2.2
2616060
SUPPORT-GENERATOR
C1.5, C2.2
C1.5, C2.2
2652656
SUPPORT
C1.5, C2.2, C3.3, C4.4
C1.5, C2.2, C3.3, C4.4
2665753
SUPPORT-BATTERY
C3.3, C4.4
C3.3, C4.4
2752430
SUPPORT
C3.3
C3.3
3015753
SUPPORT AS-PANEL
C3.3, C4.4
C3.3, C4.4
3629284
SUPPORT AS
C2.2
C2.2
2996909
SUPPORT
C4.4
C4.4
2996907
SUPPORT
C4.4
C4.4
2996906
SUPPORT
C4.4
C4.4
2996905
SUPPORT
C4.4
C4.4
2996904
SUPPORT
C4.4
C4.4
2996903
SUPPORT
C4.4
C4.4
1542974
SUPPORT
3412C
3412C
2312766
SUPPORT
3412, 3412C, C27, G3412
3412, 3412C, C27, G3412
2501025
SUPPORT-PANEL
C4.4, C6.6
C4.4, C6.6
2501026
SUPPORT-PANEL
C4.4, C6.6
C4.4, C6.6